User`s guide

Electrical Requirements
007-5483-001 15
Electrical Requirements
The SGI Virtu VN200 accepts single-phase input voltage only. It typically connects to a
single-phase or 3-phase rack power distribution unit (PDU) that outputs single-phase
220
VAC. Ensure that the required voltage is available and is within a reasonable distance
of the intended location. If it is not, the site must be wired for the required voltage.
Power Consumption for the Graphics Node
Note: Refer to “Related Publications” on page xiv, for a listing of relevant SGI Technical
Publications that can provide the electrical requirements for the other node types in the
system rack.
The system configuration used to measure the power consumption of the graphics node
listed in
Table 1-2:
CPU: 2 Intel 5482 (150W)
Memory: 16 GB ECC DDR2 800 MHz FBDIMMs using 2 GB DIMMs
HDD: 1 SATA, 80GB
•OS: Windows XP 64-bit
Stress software: CPU Burn
Fans: Two 60 x 38mm 12,000 RPM
Video: NVIDIA Quadro FX5600
Table 1-2 lists the power consumption for each graphics node.
Table 1-2 Graphics Node Power Consumption
Power (W) Current (A) Voltage (V)
Heat
Dissipation
(BTU)
Idle
302 2.52 120.5 1,030
Load
468 3.88 120.5 1,597