Technical data
88 DE5600 Drive Tray Temperature and Humidity
DE5600 Drive
Tray
Temperature
and Humidity
NOTE Converting Maximum Rate of Change requires converting between Fahrenheit
and Celsius first, and then subtracting the difference.
Table 65 Temperature Requirements and Humidity Requirements for the
DE5600 Drive Tray
DE5600 Drive
Tray Altitude
Ranges
Table 66 Altitude Ranges for the DE5600 Drive Tray
Condition Parameter Requirement
Temperature Operating range (both cabinet
and subsystem)
10°C to 35° C 50°F to 104°F)
Maximum rate of change 10°C (18°F) per hour]
Storage range –10°C to 50°C (14°F to 122°F)
Maximum rate of change 15°C (27°F) per hour
Transit range –40°C to 60°C (–40°F to 140°F)
Maximum rate of change 20°C (36°F) per hour
Relative
humidity (no
condensation)
Operating range (both cabinet
and subsystem)
20% to 80%
Storage range 10% to 90%
Transit range 5% to 90%
Operating gradient 10°C (50°F) per hour
Storage gradient 15°C (59°F) per hour
Transit gradient 20°C (68°F) per hour
Maximum dew point 26°C (79°F)
Maximum gradient 10% per hour
*If you plan to operate a system at an altitude between 1000 m to 3000 m (3280 ft to
9842 ft) above sea level, lower the environmental temperature 1.7°C (3.3°F) for
every 1000 m (3280 ft) above sea level.
Environment Altitude
Operating 30.5 m (100 ft) below sea level to 3000 m (9840 ft) above sea level
Storage 30.5 m (100 ft) below sea level to 3000 m (9840 ft) above sea level
Transit 30.5 m (100 ft) below sea level to 12,000 m (40,000 ft) above sea
level