Technical data
52 E5460 Controller-Drive Tray Altitude Ranges
E5460
Controller-Drive
Tray Altitude
Ranges
Table 35 Altitude Ranges for the E5460 Controller-Drive Tray
E5460
Controller-Drive
Tray Airflow
and Heat
Dissipation
Airflow goes from the front of the E5460 controller-drive tray to the rear of the
controller-drive tray. Allow at least 81 cm (32 in.) of clearance in front of the E5460
controller-drive tray and at least 61 cm (24 in.) of clearance behind the
controller-drive tray for service clearance, ventilation, and heat dissipation.
Relative
humidity (no
condensation)
Operating range (both cabinet
and subsystem)
20% to 80%
Storage range 10% to 90%
Transit range 5% to 90%
Operating gradient 10°C (50°F) per hour maximum
Storage gradient 15°C (59°F) per hour maximum
Transit gradient 20°C (68°F) per hour maximum
Maximum dew point 26°C (79°F)
Maximum gradient 10% per hour
If you plan to operate a system at an altitude between 1000 m to 3000 m (3280 ft to
9842 ft) above sea level, lower the environmental temperature 1.7°C (3.1°F) for
every 1000 m (3280 ft) above sea level.
Condition Parameter Requirement
Environment Altitude
Operating 30.5 m (100 ft) below sea level to 3000 m (9842 ft) above sea level
Storage 30.5 m (100 ft) below sea level to 3000 m (9842 ft) above sea level
Transit 30.5 m (100 ft) below sea level to 12,000 m (40,000 ft) above sea
level