Technical data
Chapter 4: Specifications of the E2600 Controller-Drive Tray 23
E2600
Controller-Drive
Tray
Temperature
and Humidity
NOTE Converting Maximum Rate of Change requires converting between Fahrenheit
and Celsius first, and then subtracting the difference.
Table 11 Temperature Requirements and Humidity Requirements for the E2600 Controller-Drive Tray
E2600
Controller-Drive
Tray Altitude
Ranges
Table 12 Altitude Ranges for the E2600 Controller-Drive Tray
Condition Parameter Requirement
Temperature Operating range (both cabinet and subsystem) 10°C to 35°C (50°F to 95°F)
Maximum rate of change 10°C per hour (18°F per hour)
Storage range –10°C to 50°C (14°F to 122°F)
Maximum rate of change 15°C per hour (27°F per hour)
Transit range –40°C to 60°C (–40°F to 140°F)
Maximum rate of change 20°C per hour (36°F per hour)
Relative humidity (no
condensation)
Operating range (both cabinet and subsystem) 20% to 80%
Storage range 10% to 90%
Transit range 5% to 90%
Operating gradient 10°C (50°F) per hour maximum
Storage gradient 15°C (59°F) per hour maximum
Transit gradient 20°C (68°F) per hour maximum
Maximum dew point 26°C (79°F)
Maximum gradient 10% per hour
*If you plan to operate a system at an altitude between 1000 m to 3000 m (3280 ft to 9842 ft) above sea level, lower
the environmental temperature 1.7°C (3.1°F) for every 1000 m (3280 ft) above sea level.
Environment Altitude
Operating 30.5 m (100 ft) below sea level to 3000 m (9840 ft) above sea level
Storage 30.5 m (100 ft) below sea level to 3000 m (9840 ft) above sea level
Transit 30.5 m (100 ft) below sea level to 12,000 m (40,000 ft) above sea
level