Technical data

12 Model 3040 40U Cabinet Grounding
Model 3040 40U
Cabinet
Grounding
To prevent personal injury or electrostatic discharge (ESD), make sure that the
cabinet is correctly grounded. The ground must have the correct low impedance so
that there is no build-up of voltage on any equipment or on any exposed surfaces.
Grounding is especially important to eliminate shock hazards, and to facilitate the
operation of circuit-protective devices.
Consider a low impedance grounding and lightning protection when you plan for and
install an electrical system. Your electrical contractor must meet local code
requirements and national code requirements when installing an electrical system.
NOTE Local codes and local standards might have more stringent requirements.
Always comply with local codes.
Model 3040 40U
Cabinet Power
Distribution
The Model 3040 40U cabinet has two identical AC power distribution units, each of
which has a separate power cords for each side. Depending on your configuration,
each AC power distribution unit supports either North American (USA and Canada)
components or worldwide (excluding USA and Canada) components. Each AC power
distribution unit includes these parts:
Two cords per side, NEMA L6-30P or IEC 309, for 48A PDUs
Three cords per side, for 78A PDUs
Four circuit breakers per side, 15 A each, for 48A PDUs
Six circuit breakers per side, 15 A each, for 72A PDUs
Twenty IEC 320 power outlets per side, plus an additional outlet for the optional
fan tray
NOTE For pluggable equipment, the electrical outlet must be installed near the
equipment and must be easily accessible.
E5524 controller-drive tray 0.561 554 1896
E5560 controller-drive tray 1.191 1179 4032
DE1600 drive tray 0.276 276 945
DE5600 drive tray 0.241 240 821
DE6600 drive tray (requires 72A
PDUs)
1.268 1222 4180 6.30
*The maximum ratings at 200 VAC. The Btu/Hr calculation is based on the
maximum current rating that the power distribution unit can provide.
Component KVA Watts Btu/Hr Amps (240 VAC)