SGI InfiniteStorage 4000 Series and 5000 Series Site Preparation Guide (ISSM 10.
The information in this document supports the SGI InfiniteStorage 4000 series and 5000 series storage systems (ISSM 10.86). Refer to the table below to match your specific SGI InfiniteStorage product with the model numbers used in this document.
Copyright information Copyright © 1994–2012 NetApp, Inc. All rights reserved. Printed in the U.S.A. No part of this document covered by copyright may be reproduced in any form or by any means— graphic, electronic, or mechanical, including photocopying, recording, taping, or storage in an electronic retrieval system—without prior written permission of the copyright owner.
Trademark information NetApp, the NetApp logo, Network Appliance, the Network Appliance logo, Akorri, ApplianceWatch, ASUP, AutoSupport, BalancePoint, BalancePoint Predictor, Bycast, Campaign Express, ComplianceClock, Cryptainer, CryptoShred, Data ONTAP, DataFabric, DataFort, Decru, Decru DataFort, DenseStak, Engenio, Engenio logo, E-Stack, FAServer, FastStak, FilerView, FlexCache, FlexClone, FlexPod, FlexScale, FlexShare, FlexSuite, FlexVol, FPolicy, GetSuccessful, gFiler, Go further, faster, Imagine Virtu
Table of Contents Chapter 1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Chapter 2 Specifications of the Model 3040 40U Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Model 3040 40U Cabinet Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Model 3040 40U Cabinet Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Model 3040 40U Cabinet Weights . . . .
E2600 Controller-Drive Tray Optional DC Power Connector Cables and Source Wires . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 Chapter 5 Specifications of the E2660 Controller-Drive Tray . . . . . . . . . . . . . . . . . . . . . . . 29 E2660 Controller-Drive Tray Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 E2660 Controller-Drive Tray Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 7 Specifications of the E5460 Controller-Drive Tray . . . . . . . . . . . . . . . . . . . . . . . 49 E5460 Controller-Drive Tray Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 E5460 Controller-Drive Tray Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 E5460 Controller-Drive Tray Shipping Dimensions . . . . . . . . . . . . . . . . . . . . . 51 E5460 Controller-Drive Tray Temperature and Humidity. . . . . . . . . . . . . . . . .
E5560 Controller-Drive Tray Shipping Dimensions . . . . . . . . . . . . . . . . . . . . . 71 E5560 Controller-Drive Tray Temperature and Humidity. . . . . . . . . . . . . . . . . 71 E5560 Controller-Drive Tray Altitude Ranges . . . . . . . . . . . . . . . . . . . . . . . . . 72 E5560 Controller-Drive Tray Airflow and Heat Dissipation . . . . . . . . . . . . . . . 72 E5560 Controller-Drive Tray Acoustic Noise . . . . . . . . . . . . . . . . . . . . . . . . . .
DE5600 Drive Tray Airflow and Heat Dissipation . . . . . . . . . . . . . . . . . . . . . . 89 DE5600 Drive Tray Acoustic Noise. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89 DE5600 Drive Tray Site Wiring and Power. . . . . . . . . . . . . . . . . . . . . . . . . . . . 90 DE5600 Drive Tray AC Power Input. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90 DE5600 Drive Tray Power Factor Correction . . . . . . . . . . . . . . . . . . . . . . . . . .
x Table of Contents
1 Overview of the Site Preparation Guide Use this document to prepare your site for the installation of controllers and drive trays into an industry-standard cabinet. This Site Preparation Guide includes information about the supported controllers and drive trays listed in the table below as well as key specification information for each one.
2
Specifications of the Model 3040 40U Cabinet 2 The Model 3040 40U cabinet has these standard features: A detachable rear door Standard Electronic Industry Association (EIA) support rails that provide mounting holes for installing devices into a standard 48.3-cm (19-in.
Figure 1 Components of the Model 3040 40U Cabinet – Front View and Rear View 1. Ventilation Cover 2. Interface Cable Access Openings 3. Rear Plate 4. EIA Support Rails 5. Vertical Support Rails 6. Cabinet Mounting Rails 7. Stability Foot 8. Adjustable Leveling Feet 9. Power Strip 10. AC Power Distribution Units 11. Front of the Cabinet 12.
You can configure the cabinet to meet your data storage needs. Standard cabinet configurations consist of a combination of these types of trays: Model 3040 40U Cabinet Configurations Controller tray – Contains one or two controllers, one interconnect-battery canister, and two power-fan canisters. Controller-drive tray – Contains drives, redundant cooling fans and power supplies, and, depending on the model, one or two controllers.
NOTE A 3040 40U Cabinet can hold a maximum of 20 12-drive trays or 24-drive trays. Of these trays, a maximum of 10 can be controller-drive trays, so the remaining 10 trays must be drive trays. NOTE A 3040 40U Cabinet can hold a maximum of 10 60-drive trays. Of these trays, a maximum of 5 can be controller-drive trays, so the remaining 5 trays must be drive trays.
Model 3040 40U Cabinet Weights ATTENTION Risk of damage to flooring – The weight of the cabinet might exceed the flooring load specifications. A fully-loaded 3040 40U cabinet weighs up to 1090 kg (2400 lb). Before you install your components, make sure that your flooring is strong enough to support the weight of the cabinet and its components. Record the total weight of your cabinet and its components.
Table 5 Temperature Requirements and Humidity Requirements for the Model 3040 40U Cabinet Environment Operating* Storage Transit Temperature Range Temperature Change 10°C to 35° C 10°C per hour (50°F to 95°F) (18°F per hour) –10°C to 45°C 15°C per hour (14°F to 113°F) (27°F per hour) –40°C to 65°C 20°C per hour (–40°F to 149°F) (36°F per hour) Relative Humidity 20% to 80% 10% to 90% 5% to 95% *If you plan to operate a storage array at an altitude between 1000 m to 3000 m (3280 ft to 984
Figure 3 Area Requirements for the Model 3040 40U Cabinet – Top View 1. Rear of the Cabinet 2. Required Rear Service Area – 61 cm (24 in.) 3. Cable Access 4. Roller Caster 5. Adjustable Leveling Foot 6. Required Front Service Area – 76 cm (30 in.) 7. Width of the Cabinet – 61 cm (24 in.) 8. Front of the Cabinet 9. Depth of the Cabinet – 102 cm (40 in.) 10. Computer Floor Grid – 61 cm x 61 cm (24 in. x 24 in.) 11. Total Clearance Depth – 240 cm (94 in.
Do not place anything in front of the cabinet or behind the cabinet that would interfere with air flow. The cabinet’s ventilation is essential to make sure that ambient air is available to correctly cool your storage array. Total heat dissipation is a function of the number and type of trays that are installed in the cabinet. Use the table in Model 3040 40U Cabinet Power Requirements to calculate the total heat dissipation for your configuration.
Model 3040 40U Cabinet Power Requirements Table 7 AC Power Requirements for the Model 3040 40U Cabinet Parameter Requirement Nominal voltage 200 VAC to 240 VAC Frequency 50 Hz to 60 Hz Nominal current (typical) 10.0 A to 24.0 A Varies depending upon the number and type of trays that are installed in the cabinet. The Model 3040 40U cabinet contains power strips that provide either 48A or 72A of usable power. The 48A power strips provide up to 48A of usable power through four 12A banks of power.
Component KVA Watts Btu/Hr E5524 controller-drive tray 0.561 554 1896 E5560 controller-drive tray 1.191 1179 4032 DE1600 drive tray 0.276 276 945 DE5600 drive tray 0.241 240 821 DE6600 drive tray (requires 72A PDUs) 1.268 1222 4180 Amps (240 VAC) 6.30 *The maximum ratings at 200 VAC. The Btu/Hr calculation is based on the maximum current rating that the power distribution unit can provide.
Figure 4 Circuit Breakers and Electrical Outlets for 48A PDUs Chapter 2: Specifications of the Model 3040 40U Cabinet 1. Controller Tray 2. Power Strip 3. Drive Tray 4. AC Power Distribution Unit 5.
Figure 5 Circuit Breakers and Electrical Outlets for 72A PDUs 14 1. Circuit Breakers 2.
Model 3040 40U Cabinet Power Cords and Receptacles The cabinet is equipped with two AC power distribution units. Each AC power distribution unit contains four 15-A circuit breakers on each side. Depending on your installation, the AC power distribution units in your cabinet have either North American (USA and Canada) power cords or worldwide (except USA and Canada) power cords. Connect each AC power distribution unit power cord to an independent power source outside of the cabinet.
16 Model 3040 40U Cabinet Power Cords and Receptacles
Preparing the Network for the Controllers 3 If you plan to use Ethernet connections from the storage management station to the controllers, you will use the out-of-band management method. For this configuration, meet with your network administrator before you order and install the equipment so that you can prepare for the setup and management of the devices on the IP network.
18
Specifications of the E2600 Controller-Drive Tray 4 The E2600 controller-drive tray is available in a rackmount model, with a capacity of either 12 drives or 24 drives. Figure 8 E2600 Controller-Drive Tray with 12 Drives – Front View 1. End Caps (the Left End Cap Has the Controller-Drive Tray Summary LEDs) 2. Drive Canisters Figure 9 E2600 Controller-Drive Tray with 24 Drives – Front View Chapter 4: Specifications of the E2600 Controller-Drive Tray 1.
Figure 10 E2600 Controller-Drive Tray Duplex Configuration – Rear View 1. AC Power Connector 2. AC Power Switch 3. Optional DC Power Connector and DC Power Switch Figure 11 E2600 Controller-Drive Tray Simplex Configuration – Rear View 20 1. AC Power Connector 2. AC Power Switch 3.
E2600 Controller-Drive Tray Dimensions The E2600 controller-drive tray conforms to the 48.3-cm (19.0-in.) rack standard.
E2600 Controller-Drive Tray Weight Table 9 Weights of the E2600 Controller-Drive Tray Weight Unit Maximum* Empty** Shipping*** Controller-Drive Tray, with twelve 8.89-cm (3.5-in.) 27 kg (59.52 lb) drives 8.4 kg (18.52 lb) 31.75 kg (70.0 lb) Controller-Drive Tray, with twenty-four 6.35-cm (2.5-in.) drives 10.7 kg (23.59 lb) 31.75 kg (70.0 lb) 26 kg (57.32 lb) *Maximum weight indicates a controller-drive tray with all of its drives and other components installed.
E2600 Controller-Drive Tray Temperature and Humidity NOTE Converting Maximum Rate of Change requires converting between Fahrenheit and Celsius first, and then subtracting the difference.
E2600 Controller-Drive Tray Airflow and Heat Dissipation 24 Allow at least 76 cm (30 in.) of clearance in front of the controller-drive tray and 61 cm (24 in.) behind the controller-drive tray for service clearance, ventilation, and heat dissipation. Figure 14 Airflow Through the Controller-Drive Tray with 12 Drives – Front View 1. 76 cm (30 in.) clearance in front of the cabinet 2. 61 cm (24 in.
Figure 15 Airflow Through the Controller-Drive Tray with 24 Drives – Front View 1. 76 cm (30 in.) clearance in front of the cabinet 2. 61 cm (24 in.) clearance behind the cabinet Table 13 Power and Heat Dissipation for the E2600 Controller-Drive Tray Component KVA Watts (AC) Btu/Hr Controller canisters with two power-fan canisters and 12 drives 0.400 399 1366 Controller canisters with two power-fan canisters and 24 drives 0.
E2600 Controller-Drive Tray Site Wiring and Power The E2600 controller-drive tray uses wide-ranging, redundant power supplies that automatically accommodate voltages to the AC power source or the optional –48-VDC power source. The power supplies meet standard voltage requirements for both North American (USA and Canada) operation and worldwide (except USA and Canada) operation. The power supplies use standard industrial wiring with line-to-neutral or line-to-line power connections.
Parameter Low Range High Range Maximum operating current 4.25 A* 1.68 A** Sequential Drive Group Spin 4.27 A Up 1.76 A Simultaneous Drive Spin Up 6.13 A 2.71 A System Rating Plate Label 2.9 A 7.0 A * Typical current: 100 VAC, 60 Hz at 0.87 power supply efficiency and 0.99 power factor. These numbers can vary significantly, depending upon the drives tested in the particular configuration. **Typical current: 240 VAC, 60 Hz at 0.87 power supply efficiency and 0.99 power factor.
E2600 Controller-Drive Tray Optional DC Power Connector Cables and Source Wires The E2600 controller-drive tray is shipped with –48-VDC power connector cables if the DC power option is ordered. The –48-VDC power connector cable plugs into the DC power connector on the rear of the controller-drive tray. The three source wires on the other end of the power connector cable connect the controller-drive tray to centralized DC power plant equipment, typically through a bus bar above the cabinet.
Specifications of the E2660 Controller-Drive Tray 5 The E2660 controller-drive tray is a high-density SAS 2.0 (6-Gb/s) drive enclosure with 60 near-line 3.5” SAS drives, housed in five drawers with 12 drives each. Figure 16 E2660 Controller-Drive Tray – Front View with Bezel Removed Chapter 5: Specifications of the E2660 Controller-Drive Tray 1. Drive Drawer 1 2. Drive Drawer 2 3. Drive Drawer 3 4. Drive Drawer 4 5.
Figure 17 E2660 Controller-Drive Tray – Rear View E2660 Controller-Drive Tray Dimensions 30 1. Fan Canisters 2. Power Canisters 3. Controller-Drive Tray Canisters The E2660 controller-drive tray conforms to the 48.3-cm (19.0-in.) rack standard.
E2660 Controller-Drive Tray Weight Table 16 Weights of the E2660 Controller-Drive Tray Weight Unit Maximum* E2660 controller-drive tray 105.2 kg (232 lb) Empty** Shipping*** 19.5 kg (43 lb) 193.2 kg (426 lb) *Maximum weight indicates a controller-drive tray with all of its drives and other components installed. Because drive weights can vary greatly, this value can vary from the value specified as much as 0.3 kg (0.6 lb) times the maximum number of drives per drive tray for drives weighing 0.
Table 19 Temperature Requirements and Humidity Requirements for the E2660 Controller-Drive Tray Condition Temperature Relative humidity (no condensation) Parameter Requirement Operating range (both cabinet 10°C to 35°C (50°F to 95°F) and subsystem) Maximum rate of change 10°C per hour (18°F) per hour Storage range –10°C to 50°C (14°F to 122°F) Maximum rate of change 15°C per hour (27°F) per hour Transit range –40°C to 60°C (–40°F to 140°F) Maximum rate of change 20°C per hour (36°F) per hour
E2660 Controller-Drive Tray Airflow and Heat Dissipation Figure 19 Airflow Through the E2660 Controller-Drive Tray – Front View 1. 81 cm (32 in.) clearance in front of the cabinet 2. 61 cm (24 in.) clearance behind the cabinet The tabulated power and heat dissipation values in the following table are the maximum measured operating power. Table 21 Power Ratings and Heat Dissipation for the E2660 Controller-Drive Tray Unit KVA E2660 controller-drive tray with two power 1.
E2660 Controller-Drive Tray Acoustic Noise E2660 Controller-Drive Tray Site Wiring and Power Table 22 Acoustic Noise at 25°C for the E2660 Controller-Drive Tray Measurement Level Sound power (standby operation) 6.5 bels Sound power (normal operation) 6.8 bels Sound pressure 68 dBA The E2660 controller-drive tray uses wide-ranging, redundant power supplies that automatically accommodate voltages to the AC power source.
E2660 Controller-Drive Tray Power Input Each power supply contains one 15-A slow-blow fuse. Table 23 AC Power Requirements for the E2660 Controller-Drive Tray Parameter High Range Nominal voltage 240 VAC Frequency 50-60 Hz Idle current 4.14 A Maximum operating current 4.16 A Maximum surge current 7.
36 E2660 Controller-Drive Tray AC Power Cords and Receptacles
Specifications of the E5400 Controller-Drive Tray 6 The E5400 controller-drive tray is available in a rackmount model, with a capacity of either 12 drives or 24 drives. The E5400 controller-drive tray is a compact, rackmounted unit that provides high-capacity disk storage for Fibre Channel, Infiniband, and iSCSI environments, depending on the choice of the host interface card. Figure 20 E5400 Controller-Drive Tray with 12 Drives – Front View 1.
Figure 22 E5400 Controller-Drive Tray – Rear View E5400 Controller-Drive Tray Dimensions 38 1. AC Power Connector on the AC Power-Fan Canister 2. AC Power Switch 3. DC Power Connector and DC Power Switch on the Optional DC Power-Fan Canister The E5400 controller-drive tray conforms to the 48.3-cm (19.0-in.) rack standard.
Figure 24 Dimensions of the E5400 Controller-Drive Tray (24-Drive Model) – Front View Chapter 6: Specifications of the E5400 Controller-Drive Tray 39
E5400 Controller-Drive Tray Weight Table 24 Weights of the E5412 and E5424 Controller-Drive Trays Weight Unit Maximum* Empty** Shipping*** E5412 controller-drive tray, with twelve 8.89-cm (3.5-in.) drives 27 kg (59.52 lb) 8.4 kg (18.52 lb) 31.75 kg (70.0 lb) E5424 controller-drive tray, with twenty-four 6.35-cm (2.5-in.) drives 26 kg (57.32 lb) 10.7 kg (23.59 lb) 31.75 kg (70.0 lb) *Maximum weight indicates a controller-drive tray with all of its drives and other components installed.
E5400 Controller-Drive Tray Shipping Dimensions Table 25 Shipping Carton Dimensions for the E5412 and E5424 Controller-Drive Trays Controller-Drive Tray Height Width Depth E5412 controller-drive tray with twelve 3.5-in. drives 24.13 cm (9.5 in.) 63.50 cm (25 in.) 58.42 cm (23 in.) E5424 controller-drive tray with twenty-four 2.5-in. drives 24.13 cm (9.5 in.) 68.58 cm (27 in.) 58.42 cm (23 in.
Condition Relative humidity (no condensation) Parameter Requirement Operating range (both cabinet 20% to 80% and subsystem) Storage range 10% to 90% Transit range 5% to 90% Operating gradient 10°C (50°F) per hour maximum Storage gradient 15°C (59°F) per hour maximum Transit gradient 20°C (68°F) per hour maximum Maximum dew point 26°C (79°F) Maximum gradient 10% per hour *If you plan to operate a system at an altitude between 1000 m to 3000 m (3280 ft to 9842 ft) above sea level, lower the e
Figure 25 Airflow Through the E5512 Controller-Drive Tray with 12 Drives – Front View 1. 76 cm (30 in.) clearance in front of the cabinet 2. 61 cm (24 in.) clearance behind the cabinet Figure 26 Airflow Through the E5524 Controller-Drive Tray with 24 Drives – Front View 1. 76 cm (30 in.
2. 61 cm (24 in.) clearance behind the cabinet Table 28 Power and Heat Dissipation for the E5512 and E5524 Controller-Drive Trays Component E5400 Controller-Drive Tray Acoustic Noise E5500 Controller-Drive Tray Site Wiring and Power KVA Watts (AC) Btu/Hr Controller canisters with two power-fan canisters and 12 drives 0.589 589 2016 Controller canisters with two power-fan canisters and 24 drives 0.
E5400 Controller-Drive Tray Power Input Power interruptions – The controller-drive tray can withstand these applied voltage interruptions: — Input transient – 50 percent of the nominal voltage — Duration – One-half cycle — Frequency – Once every 10 seconds Power failures – If a total power failure occurs, the controller-drive tray automatically performs a power-on recovery sequence without operator intervention. AC Power Input Each power supply contains one 10-A slow-blow fuse.
E5400 Controller-Drive Tray AC Power Cords and Receptacles Each E5400 controller-drive tray is shipped with two AC power cords, which use the standard AC outlets in the destination country. Each AC power cord connects one of the power supplies in the drive tray to an independent, external AC power source, such as a wall receptacle, or to any uninterruptible power supply (UPS).
Two (or, optionally, four) DC power connector cables are provided with each controller-drive tray. Two DC power connectors are on the two DC power supplies on the rear of each controller-drive tray if additional redundancy is required. NOTE It is not mandatory that you connect the second DC power connection on the DC power supplies of the controller-drive tray. The second DC power connection is provided for additional redundancy only and can be connected to a second DC power bus.
48 E5400 Controller-Drive Tray Optional DC Power Connector Cables and Source Wires
Specifications of the E5460 Controller-Drive Tray 7 The E5460 controller-drive tray is a high-density SAS 2.0 (6-Gb/s) drive enclosure with 60 near-line 3.5 in. SAS drives, housed in five drawers with 12 drives each. Figure 27 E5460 Controller-Drive Tray – Front View with Bezel Removed 1. Drive Drawer 1 2. Drive Drawer 2 3. Drive Drawer 3 4. Drive Drawer 4 5. Drive Drawer 5 Figure 28 E5460 Controller-Drive Tray – Rear View 1.
E5460 Controller-Drive Tray Dimensions The E5460 controller-drive tray conforms to the 48.3-cm (19.0-in.) rack standard. Figure 29 Dimensions of the E5460 Controller-Drive Tray – Front View E5460 Controller-Drive Tray Weight Table 31 Weights of the E5460 Controller-Drive Tray Weight Unit Maximum* E5460 controller-drive tray 105.2 kg (232 lb) Empty** 19.5 kg (132 lb) Shipping*** 193.2 kg (426 lb) *Maximum weight indicates a controller-drive tray with all of its drives and other components installed.
Table 32 Component Weights of the E5460 Controller-Drive Tray Component E5460 Controller-Drive Tray Shipping Dimensions E5460 Controller-Drive Tray Temperature and Humidity Weight Controller canister 2.99 kg (6.60 lb) Power canister 2.5 kg (5.5 lb) Fan canister Approximately 1 kg (2.16 lb) Drive 0.74 kg (1.64 lb) Table 33 Shipping Carton Dimensions for the E5460 Controller-Drive Tray Height 48.26 cm (19 in.) Width Depth 60.96 cm (24.00 in.) 100.97 cm (39.75 in.
Condition Relative humidity (no condensation) Parameter Requirement Operating range (both cabinet 20% to 80% and subsystem) Storage range 10% to 90% Transit range 5% to 90% Operating gradient 10°C (50°F) per hour maximum Storage gradient 15°C (59°F) per hour maximum Transit gradient 20°C (68°F) per hour maximum Maximum dew point 26°C (79°F) Maximum gradient 10% per hour If you plan to operate a system at an altitude between 1000 m to 3000 m (3280 ft to 9842 ft) above sea level, lower the en
Figure 30 Airflow Through the E5460 Controller-Drive Tray – Front View 1. 81 cm (32 in.) clearance in front of the cabinet 2. 61 cm (24 in.) clearance behind the cabinet The tabulated power and heat dissipation values in the following table are the maximum measured operating power.
E5460 Controller-Drive Tray Acoustic Noise E5460 Controller-Drive Tray Site Wiring and Power Table 37 Acoustic Noise at 25°C for the E5460 Controller-Drive Tray Measurement Level Sound power (standby operation) 6.5 bels Sound power (normal operation) 6.8 bels Sound pressure 68 dBA The E5460 controller-drive tray uses wide-ranging, redundant power supplies that automatically accommodate voltages to the AC power source.
E5460 Controller-Drive Tray Power Input Each power supply contains one 15-A slow-blow fuse. Table 38 AC Power Requirements for the E5460 Controller-Drive Tray Parameter Low Range High Range Nominal voltage 200 VAC 240 VAC Frequency 50 Hz 60 Hz Typical Operating Current 4.9 A 5.75 A System Nameplate Rating 6.3 A 7.
56 E5460 Controller-Drive Tray AC Power Cords and Receptacles
8 Specifications of the E5500 Controller-Drive Tray The E5500 controller-drive tray is available in a rackmount model, with a capacity of either 12 drives or 24 drives. The E5500 controller-drive tray is a compact, rackmounted unit that provides high-capacity disk storage for SAS and Infiniband environments, depending on the choice of the host interface card. Figure 31 E5500 Controller-Drive Tray with 12 Drives – Front View 2 1 3 ! 97001-02 1.
Figure 33 E5500 Controller-Drive Tray – Rear View E5500 Controller-Drive Tray Dimensions 1. AC Power Connector on the AC Power-Fan Canister 2. AC Power Switch 3. DC Power Connector and DC Power Switch on the Optional DC Power-Fan Canister The E5500 controller-drive tray conforms to the 48.3-cm (19.0-in.) rack standard. Figure 34 Dimensions of the E5500 Controller-Drive Tray (12-Drive Model) – Front View 97007-01 48.26 cm (19.00 in.) 8.64 cm (3.40 in.) 55.25 cm (21.75 in.
Figure 35 Dimensions of the E5500 Controller-Drive Tray (24-Drive Model) – Front View Chapter 8: Specifications of the E5500 Controller-Drive Tray 59
E5500 Controller-Drive Tray Weight Table 39 Weights of the E5512 and E5524 Controller-Drive Trays Weight Unit Maximum* Empty** Shipping*** E5512 controller-drive tray, with twelve 8.89-cm (3.5-in.) drives 27 kg (59.52 lb) 8.4 kg (18.52 lb) 31.75 kg (70.0 lb) E5524 controller-drive tray, with twenty-four 6.35-cm (2.5-in.) drives 26 kg (57.32 lb) 10.7 kg (23.59 lb) 31.75 kg (70.0 lb) *Maximum weight indicates a controller-drive tray with all of its drives and other components installed.
E5500 Controller-Drive Tray Shipping Dimensions Table 40 Shipping Carton Dimensions for the E5512 and E5524 Controller-Drive Trays Controller-Drive Tray Height Width Depth E5512 controller-drive tray with twelve 3.5-in. drives 24.13 cm (9.5 in.) 63.50 cm (25 in.) 58.42 cm (23 in.) E5524 controller-drive tray with twenty-four 2.5-in. drives 24.13 cm (9.5 in.) 68.58 cm (27 in.) 58.42 cm (23 in.
Condition Relative humidity (no condensation) Parameter Requirement Operating range (both cabinet 20% to 80% and subsystem) Storage range 10% to 90% Transit range 5% to 90% Operating gradient 10°C (50°F) per hour maximum Storage gradient 15°C (59°F) per hour maximum Transit gradient 20°C (68°F) per hour maximum Maximum dew point 26°C (79°F) Maximum gradient 10% per hour *If you plan to operate a system at an altitude between 1000 m to 3000 m (3280 ft to 9842 ft) above sea level, lower the e
Figure 36 Airflow Through the E5512 Controller Tray with 12 Drives – Front View 1. 76 cm (30 in.) clearance in front of the cabinet 2. 61 cm (24 in.) clearance behind the cabinet Figure 37 Airflow Through the E5524 Controller-Drive Tray with 24 Drives – Front View 1. 76 cm (30 in.) clearance in front of the cabinet 2. 61 cm (24 in.
Table 43 Power and Heat Dissipation for the E5512 and E5524 Controller-Drive Trays Component E5500 Controller-Drive Tray Acoustic Noise KVA Watts (AC) Btu/Hr Controller canisters with two power-fan canisters and 12 drives 0.674 670 2293 Controller canisters with two power-fan canisters and 24 drives 0.561 554 1896 Table 44 Acoustic Noise at 25°C for the E5512 and E5524 Controller-Drive Trays Measurement Level Sound power (standby operation) 6.
E5500 Controller-Drive Tray Power Input Power interruptions – The controller-drive tray can withstand these applied voltage interruptions: — Input transient – 50 percent of the nominal voltage — Duration – One-half cycle — Frequency – Once every 10 seconds Power failures – If a total power failure occurs, the controller-drive tray automatically performs a power-on recovery sequence without operator intervention. AC Power Input Each power supply contains one 10-A slow-blow fuse.
E5500 Controller-Drive Tray AC Power Cords and Receptacles Each E5500 controller-drive tray is shipped with two AC power cords, which use the standard AC outlets in the destination country. Each AC power cord connects one of the power supplies in the drive tray to an independent, external AC power source, such as a wall receptacle, or to any uninterruptible power supply (UPS).
Two (or, optionally, four) DC power connector cables are provided with each controller-drive tray. Two DC power connectors are on the two DC power supplies on the rear of each controller-drive tray if additional redundancy is required. NOTE It is not mandatory that you connect the second DC power connection on the DC power supplies of the controller-drive tray. The second DC power connection is provided for additional redundancy only and can be connected to a second DC power bus.
68 E5500 Controller-Drive Tray Optional DC Power Connector Cables and Source Wires
Specifications of the E5560 Controller-Drive Tray 9 The E5560 controller-drive tray is a high-density SAS 2.0 (6-Gb/s) drive enclosure with 60 near-line 3.5 in. SAS drives, housed in five drawers with 12 drives each. Figure 38 E5560 Controller-Drive Tray – Front View with Bezel Removed 1. Drive Drawer 1 2. Drive Drawer 2 3. Drive Drawer 3 4. Drive Drawer 4 5. Drive Drawer 5 Figure 39 E5560 Controller-Drive Tray – Rear View Chapter 9: Specifications of the E5560 Controller-Drive Tray 1.
E5560 Controller-Drive Tray Dimensions The E5560 controller-drive tray conforms to the 48.3-cm (19.0-in.) rack standard. Figure 40 Dimensions of the E5560 Controller-Drive Tray – Front View E5560 Controller-Drive Tray Weight Table 46 Weights of the E5560 Controller-Drive Tray Weight Unit Maximum* E5560 controller-drive tray 105.2 kg (232 lb) Empty** 19.5 kg (43 lb) Shipping*** 193.2 kg (426 lb) *Maximum weight indicates a controller-drive tray with all of its drives and other components installed.
Table 47 Component Weights of the E5560 Controller-Drive Tray Component E5560 Controller-Drive Tray Shipping Dimensions E5560 Controller-Drive Tray Temperature and Humidity Weight Controller canister 2.99 kg (6.60 lb) Power canister 2.5 kg (5.5 lb) Fan canister Approximately 1 kg (2.16 lb) Drive 0.74 kg (1.64 lb) Table 48 Shipping Carton Dimensions for the E5560 Controller-Drive Tray Height 48.26 cm (19 in.) Width Depth 60.96 cm (24.00 in.) 100.97 cm (39.75 in.
Condition Relative humidity (no condensation) Parameter Requirement Operating range (both cabinet 20% to 80% and subsystem) Storage range 10% to 90% Transit range 5% to 90% Operating gradient 10°C (50°F) per hour maximum Storage gradient 15°C (59°F) per hour maximum Transit gradient 20°C (68°F) per hour maximum Maximum dew point 26°C (79°F) Maximum gradient 10% per hour If you plan to operate a system at an altitude between 1000 m to 3000 m (3280 ft to 9842 ft) above sea level, lower the en
Figure 41 Airflow Through the E5560 Controller-Drive Tray – Front View 1. 81 cm (32 in.) clearance in front of the cabinet 2. 61 cm (24 in.) clearance behind the cabinet The tabulated power and heat dissipation values in the following table are the maximum measured operating power.
E5560 Controller-Drive Tray Acoustic Noise E5560 Controller-Drive Tray Site Wiring and Power Table 52 Acoustic Noise at 25°C for the E5560 Controller-Drive Tray Measurement Level Sound power (standby operation) 6.5 bels Sound power (normal operation) 6.8 bels Sound pressure 68 dBA The E5560 controller-drive tray uses wide-ranging, redundant power supplies that automatically accommodate voltages to the AC power source.
E5560 Controller-Drive Tray Power Input Each power supply contains one 15-A slow-blow fuse. Table 53 AC Power Requirements for the E5560 Controller-Drive Tray Parameter Low Range High Range Nominal voltage 200 VAC 240 VAC Frequency 50 Hz 60 Hz Maximum Operating Current N/A 7.84 A System Nameplate Rating 6.3 A 7.
76 E5560 Controller-Drive Tray AC Power Cords and Receptacles
Specifications of the DE1600 Drive Tray 10 The DE1600 drive tray contains Serial Attached SCSI (SAS) drives. Each DE1600 drive tray contains these components: A maximum of 12 drives One or two power-supply fan canisters One or two environmental services module (ESM) canisters Figure 42 DE1600 Drive Tray – Front View 1. End Caps (the Left End Cap Has the Drive Tray LEDs) 2. Drives 3. Right End Cap Figure 43 DE1600 Drive Tray – Rear View 1. ESM A Canister 2. ESM B Canister 3.
Figure 44 DE1600 Drive Tray – Power Source Options Rear View DE1600 Drive Tray Dimensions 78 1. AC Power Connector on the AC Power-Fan Canister 2. AC Power Switch 3. DC Power Switch on an Optional DC Power-Fan Canister 4.
DE1600 Drive Tray Weight Table 54 Weights of the DE1600 Drive Tray Weight Unit Maximum* DE1600 drive tray 27 kg (59.52 lb) Empty** Shipping*** 8.4 kg (18.52 lb) 31.75 kg (70.0 lb) *Maximum weight indicates a drive tray with all of its drives and other components installed. Because drive weights can vary greatly, this value can vary from the value specified as much as 0.3 kg (0.6 lb) times the maximum number of drives per drive tray for 3.5-in. SAS drives.
Table 57 Temperature Requirements and Humidity Requirements for the DE1600 Drive Tray Condition Temperature Relative humidity (no condensation) Parameter Requirement Operating range (both cabinet and subsystem) 10°C to 35°C (50°F to 104°F) Maximum rate of change 10°C (18°F) per hour Storage range –10°C to 50°C (14°F to 122°F) Maximum rate of change 15°C (27°F) per hour Transit range –40°C to 60°C (–40°F to 140°F) Maximum rate of change 20°C (36°F) per hour Operating range (both cabinet and
Figure 46 Airflow Through the DE1600 Drive Tray – Front View 1. 76 cm (30 in.) clearance in front of the cabinet 2. 61 cm (24 in.) clearance behind the cabinet The tabulated power and heat dissipation values in the following table are the maximum measured operating power. Table 59 Power Ratings and Heat Dissipation for the DE1600 Drive Tray Unit DE1600 drive tray DE1600 Drive Tray Acoustic Noise KVA 0.
DE1600 Drive Tray Site Wiring and Power The DE1600 drive tray uses wide-ranging, redundant power supplies that automatically accommodate voltages to the AC power source or the optional –48-VDC power source. The power supplies meet standard voltage requirements for both North American (USA and Canada) operation and worldwide (except USA and Canada) operation. The power supplies use standard industrial wiring with line-to-neutral or line-to-line power connections.
Table 61 AC Power Requirements for the DE1600 Drive Tray Parameter Low Range High Range Nominal voltage 100 VAC 240 VAC Frequency 50 to 60 Hz 50 to 60 Hz Idle current 2.96 A* 1.23 A** Maximum operating current 3.03 A* 1.26 A** Sequential Drive Group Spin Up 4.23 A 1.76 A Simultaneous Drive Spin Up 4.43 A 1.83 A System Rating Plate Label 7.0 A 2.9 A * Typical current: 100 VAC, 60 Hz at 0.87 power supply efficiency and 0.99 power factor.
DE1600 Drive Tray Optional DC Power Connector Cables and Source Wires The DE1600 drive tray is shipped with –48-VDC power connector cables if the DC power option is ordered. The –48-VDC power connector cable plugs into the DC power connector on the rear of the drive tray. The three source wires on the other end of the power connector cable connect the drive tray to centralized DC power plant equipment, typically through a bus bar above the cabinet.
Specifications of the DE5600 Drive Tray 11 The DE5600 drive tray contains Serial Attached SCSI (SAS) drives. Each DE5600 drive tray contains these components: A maximum of 24 drives One or two power-supply fan canisters One or two environmental services module (ESM) canisters Figure 47 DE5600 Drive Tray – Front View 1. Left End Cap (Has the Drive Tray LEDs) 2. Drives 3. Right End Cap Figure 48 DE5600 Drive Tray – Rear View 1. ESM A Canister 2. ESM B Canister 3.
Figure 49 DE5600 Drive Tray Power Source Options – Rear View DE5600 Drive Tray Dimensions 86 1. AC Power Switch on the AC Power-Fan Canister 2. AC Power Connector 3. DC Power Switch on an Optional DC Power-Fan Canister 4.
DE5600 Drive Tray Weight Table 62 Weights of the DE5600 Drive Tray Weight Unit Maximum* DE5600 drive tray 26 kg (57.32 lb) Empty** Shipping*** 21.70 kg (47.84 lb) 31.75 kg (70.0 lb) *Maximum weight indicates a drive tray with all of its drives and other components installed. Because drive weights can vary greatly, this value can vary from the value specified as much as 0.08 kg (0.18 lb) times the maximum number of drives per drive tray for 2.5-in. SAS drives.
DE5600 Drive Tray Temperature and Humidity NOTE Converting Maximum Rate of Change requires converting between Fahrenheit and Celsius first, and then subtracting the difference.
DE5600 Drive Tray Airflow and Heat Dissipation Airflow goes from the front of the drive tray to the rear of the drive tray. Allow at least 76 cm (30 in.) of clearance in front of the drive tray and at least 61 cm (24 in.) of clearance behind the drive tray for service clearance, ventilation, and heat dissipation. Figure 51 Airflow Through the DE5600 Drive Tray – Front View 1. 76 cm (30 in.) clearance in front of the cabinet 2. 61 cm (24 in.
DE5600 Drive Tray Site Wiring and Power The DE5600 drive tray uses wide-ranging, redundant power supplies that automatically accommodate voltages to the AC power source or the optional –48-VDC power source. The power supplies meet standard voltage requirements for both North American (USA and Canada) operation and worldwide (except USA and Canada) operation. The power supplies use standard industrial wiring with line-to-neutral or line-to-line power connections.
Table 69 AC Power Requirements for the DE5600 Drive Tray Parameter Low Range High Range Nominal voltage 100 VAC 240 VAC Frequency 50 to 60 Hz 50 to 60 Hz Idle current 2.96 A* 1.23 A** Maximum operating current 3.03 A* 1.26 A** Sequential Drive Group Spin Up 4.23 A 1.76 A Simultaneous Drive Spin Up 4.43 A 1.83 A System Rating Plate Label 7.0 A 2.9 A * Typical current: 100 VAC, 60 Hz at 0.87 power supply efficiency and 0.99 power factor.
DE5600 Drive Tray Optional DC Power Connector Cables and Source Wires The DE5600 drive tray is shipped with –48-VDC power connector cables if the DC power option is ordered. The –48-VDC power connector cable plugs into the DC power connector on the rear of the drive tray. The three source wires on the other end of the power connector cable connect the drive tray to centralized DC power plant equipment, typically through a bus bar above the cabinet.
Specifications of the DE6600 Drive Tray 12 The DE6600 drive tray is a high-density SAS 2.0 (6Gb/s) drive enclosure with 60 near-line 3.5” SAS drives, housed in five drawers with 12 drives each. The DE6600 drive tray contains these components: Up to 60 SAS drives Two power canisters Two fan canisters Two environmental services module (ESM) canisters Figure 52 DE6600 Drive Tray – Front View with Bezel Removed Chapter 12: Specifications of the DE6600 Drive Tray 1. Drive Drawer 1 2.
Figure 53 DE6600 Drive Tray – Rear View 1. Fan Canisters 2. Power Canisters 3. ESM Canisters An AC power source supplies power to the power canister. Figure 54 Power Source Options for the DE6600 Drive Tray – Rear View 1. AC Power Switch on the Power Canister The drive trays come with drive interface ports that enable you to establish up to four drive channels when using the CE7900 controller tray for your disk storage solution.
DE6600 Drive Tray Dimensions The DE6600 drive tray is only available as a rackmount model that conforms to the 100-cm (40.0-in.) rack depth. Figure 55 Dimensions of the DE6600 Drive Tray – Front View DE6600 Drive Tray Weight Table 70 Weights of the DE6600 Drive Tray Weight Unit Maximum* DE6600 drive tray Empty** Shipping*** 105.2 kg (232 lb) 19.5 kg (43 lb) 193.2 kg (426 lb) *Maximum weight indicates a drive tray with all of its drives and other components installed.
Table 71 Component Weights of the DE6600 Drive Tray Component DE6600 Drive Tray Shipping Dimensions ESM canister 1.65 kg (3.64 lb) Power canister 2.5 kg (5.5 lb) Fan canister Approximately 1 kg (2.16 lb) Drive 0.74 kg (1.64 lb) Table 72 Shipping Carton Dimensions for the DE6600 Drive Tray Height 48.26 cm (19 in.) DE6600 Drive Tray Temperature and Humidity Weight Width Depth 60.96 cm (24.00 in.) 100.97 cm (39.75 in.
DE6600 Drive Tray Altitude Ranges DE6600 Drive Tray Airflow and Heat Dissipation Table 74 Altitude Ranges for the DE6600 Drive Tray Environment Altitude Operating 30.5 m (100 ft) below sea level to 3000 m (9842 ft) above sea level Storage 30.5 m (100 ft) below sea level to 3000 m (9842 ft) above sea level Transit 30.5 m (100 ft) below sea level to 12,000 m (40,000 ft) above sea level Airflow goes from the front of the drive tray to the rear of the drive tray. Allow at least 81 cm (32 in.
Table 75 Power Ratings and Heat Dissipation for the DE6600 Drive Tray Unit KVA DE6600 drive tray with two power 1.268 supplies, two ESMs, 60 drives (Seagate 2000-Gb SAS drives and controllers), and two fan canisters, full speed DE6600 Drive Tray Acoustic Noise DE6600 Drive Tray Site Wiring and Power Watts (AC) 1222 Btu/hr 4180 Table 76 Sound Levels for the DE6600 Drive Tray Measurement Level Sound power (standby operation) 6.5 bels Sound power (normal operation) 6.
DE6600 Drive Tray Power Input Power interruptions – The drive tray can withstand these applied voltage interruptions: — Input transient – 50 percent of the nominal voltage — Duration – One-half cycle — Maximum frequency – Once every 10 seconds Power failures – If a total power failure occurs, the drive tray automatically performs a power-on recovery sequence without operator intervention after the power is restored. Each power supply contains one 15-A slow-blow fuse.
100 DE6600 Drive Tray AC Power Cords and Receptacles
Regulatory Compliance Statements FCC Radio Frequency Interference Statement This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the Federal Communications Commission (FCC) Rules. These limits are designed to provide reasonable protection against harmful interference in a commercial installation.
This Class A digital apparatus meets all requirements of the Canadian Interference-Causing Equipment Regulations. Cet appareil numérique de la classé A respecte toutes les exigences du Règlement sure le matèriel brouilleur du Canada.
Copyright © 2012 NetApp, Inc. All rights reserved.