Specifications
PO Box 3526, Bellevue, WA. 98009 13737 SE 26
th
St. Bellevue, WA. 98005
Toll Free: 800-259-7331 * Phone: 425-746-6310 * Fax: 425-746-6384
www.sgcworld.com * Email: sgc@sgcworld.com
© 2003 SGC Inc. 42
5.1.2 Impedance Detector
RF transformers T1 and T3 drive the impedance bridge that is
balanced at 50 ohms. T3 samples the line current and thus D7 out-
puts a negative DC level proportional to line current. A tertiary
winding on transformer T1 provides a line voltage sample to D2
that provides a positive voltage proportional to line voltage. R18
and R11 act as a summing network for the current and voltage
signals, with ratios chosen, such that at 50 ohms, the summed
signals result in a balanced or zero voltage condition. If the line
impedance goes too high, the signal from the voltage sensor will be
relatively higher than the current sensor, which will result in a net
positive output voltage from the summing network. Similarly, a
low line impedance will result in more output from the current
sensor, resulting in a net negative output voltage from the
summing network. The summing network output is shifted to a 0 to
5v range, then fed to the processor’s A to D converter port, and
used within the micro-controller.










