Specifications

The KT-300 is designed to
meet the highest standards of
access control and point
monitoring applications. The
KT-300 controls 2 doors and
can easily link to a network
controlling thousands of doors.
KT-300
Door Controller
SOURCE BOOK
38
ACCESS CONTROL PRODUCTS
KT-100
Mini Door Controller
The new KT-100 Mini Door Controller is a
compact, versatile powerhouse with a space-
saving design that incorporates all the
components and equipment found in much larger
controllers. It includes a 2-reader interface and all
the inputs and outputs necessary to manage one
door, plus the flexibility to easily link to a network
controlling up to 64 doors (128 readers
entry/exit). It also has a storage for 6,000 users
and 3,000 events locally. Reliable, versatile, the
KT-100 is the ultimate access control reader.
37
FEATURES
KT-100 Mini Door Controller
Flash memory programming
Fast communication speed
Trouble reporting
Interfaces with external
alarm system
Higher security provided by a
concealed door relay module
Auxiliary relay to arm/disarm an
alarm system, requires Kantech
EntraPass Corporate
Edition software
Supports multiple reader types
AVAILABLE
ACCESSORIES
Models
MUSB-1WHT White surface-mount box
VC-485 RS232/RS485 multi-
function communication
device
USB-485 USB to RS485
communication interface
Input power 9.5 to 14 VDC
Battery backup 1 lithium battery, up to 10 year retention
Dimensions (H·W·D) 4.5” x 2.75” x 1.25” (11.4 x 7.0 x 3 cm)
Operating temperatures From 35° F to 110° F (2° C to 40° C ), 5% to 95% RH
Reader types Wiegand, proximity, bar code, magnetic, integrated
keypad and others
Monitored points (inputs) 4 monitored points
Points maximum wiring 2,000‘ (600m) – #22AWG
Door strike power 12 VDC, 250 mA each, supervised
Auxiliary outputs (LED, BUZ) 2 outputs, 25 mA max, 12 VDC each
Relay outputs (R1 ,R2 , R3 , R4) 2 control relay outputs, 12 VDC, 25 mA totals each
2 relay outputs, 30 VAC/DC, 50 mA each, two opto-isolated
contacts per relay
Reader power outputs 5 VDC @150 mA total, protected
Communication ports RS-485
Communication speed Up to 115,200 bps (automatic detection)
Firmware Flash memory 64K
RAM memory 128K, protected by a lithium battery
Network autonomy Distributed data and processing
Certifications/Listing FCC Part 15, Class B
TECHNICAL
SPECIFICATIONS
KT-PC4204 4-relay and COMBUS additional power supply module.
Current draw: 30mA (from COMBUS). 40 VA, 16 VAC transformer
required, maximum 12 V, 7 Ah battery required. 4 programmable
relay form ‘C’ contacts rated 2 A. Tamper contact input. (UL, FCC)
KT-PC4216 16-output module. Current draw:15 mA (from COMBUS).
Output 12 VDC, 50 mA each, power drawn from COMBUS.
Tamper contact input. (UL, FCC)
KT-PC4108 8-input module. Current draw: 30 mA (from COMBUS).
AUX power 12 VDC, 250 mA max., drawn from COMBUS.
Tamper contact input. (UL, FCC)
KT-LCD4501 LCD time/date display for Time and Attendance.
Current draw: 50 mA (from COMBUS). (UL, FCC)
Input power 16 VAC, 40 VA, class 2 transformer
Battery backup 1 battery 12 V, 7 Ah, supervised, provides operation for
up to 12 hours
Cabinet dimensions (H·W·D) 11-3/4” x 11-3/8” x 3” (29.9 x 28.8 x 7.7 cm)
Operating temperatures From 35° F to 110° F (2° C to 40° C)
Reader types Wiegand, proximity, bar code, magnetic, integrated keypad
and others
Monitored points (inputs) 8 monitored points, expandable to 16
Door strike power 12 VDC, 250 mA each, supervised
Auxiliary outputs (LED, BUZ) 4 outputs, 25 mA max each, open collector
Control relay outputs (RL1, RL2) 2 control relay outputs, 12 VDC, 25 mA total each,
open collector
Auxiliary power output 12 VDC @ 125 mA max, protected and supervised
Reader power outputs 12 VDC and 5 VDC @ 175 mA total, protected and supervised
Communication ports RS-232, RS-485 and COMBUS
Communication speed Up to 115,200 bps (automatic detection)
Firmware Flash memory 128K
RAM memory 128K (512K unit available), protected by a lithium battery
Network autonomy Distributed data and processing
Certifications UL294, FCC
TECHNICAL
SPECIFICATIONS
FEATURES
KT-300 Door Controller
Flash memory programming
Fast communication speed
Trouble reporting
COMBUS expansion with additional inputs,
outputs, relays and LCD keypads for time and
attendance applications
Supports multiple reader types
AVAILABLE
ACCESSORIES
Models
KT-300/128k Door controller with 128K memory including
KT-300CAB, KT-300ACC and KT-300LOCK
KT-300/512k Door controller with 512K memory including
KT-300CAB, KT-300ACC and KT-300LOCK
KT-300PCB/128k KT-300/128K PCB only and KT-300ACC
accessory kit
KT-300PCB/512k KT-300/512K PCB only and KT-300ACC
accessory kit
KT-300ACC Accessory kit including: 2x1.0k ohms,
10 x 5.6 k ohms, 2 x 120 ohms, PCB standoffs,
lock hole cover, ground wire and screwdriver
KT-RM1 External isolation relay SPDT for KT-300
outputs controlled by relays (RL1/RL2)
KT-300CAB KT-300 black metal cabinet including
KT-300LOCK
KT-4051CAB Standard black metal cabinet for Kantech
modules (order keylock separately)
16-13/16” x 10-3/8” x 4-1/8”
(42.7 H x 26.4 W x 14.4 D cm)
KT-300LOCK Keylock for KT-300CAB and KT-4051CAB metal
cabinet (2 keys/same as KT-200)
KT-300TAMP Tamper switch for KT-300CAB and
KT-4051CAB metal cabinet
TR1637W/CSA Transformer, wire-in,110 /16 VAC (37 VA) CSA
TR1640P/CSA Transformer, plug-in, 110 /16 VAC (40 VA) CSA
TR1640P/UL Transformer, plug-in, 110 /16 VAC (40 VA) UL
Access Control Section.qxd 1/30/03 10:13 PM Page 4