Specifications

26
7.12 Silent Knight FSK1, FSK2
7.12.1Silent Knight FSK1 Protocol
ERRLssssAAAAAAXXssss[DC4]
Where:
E FSK protocol identifier
RR Receiver number
L Line number
s Spaces
AAAAAA Account number (if the account is 4 or 5
digits, the leading “A”s will be replaced by
spaces)
XX Alarm code
Possible alarm codes are as follows:
00 Alarm Panic
01-08 Alarm 01-08
09 Holdup
10-19 Alarm 10-19
30 Test code
31 Trouble line 1
32 Trouble line 2
33 Expand trouble
34 Forced access
35 Restore line 1
36 Restore line 2
37 Expand restore
38 Cancel code
39 Data lost
40 Closing
41-49 Closing 1-9
50-59 Bypass 10-19
60 Trouble AC
61-68 Trouble 1-8
69 Trouble bat
70 Restore AC
71-78 Restore 1-8
79 Restore bat
80 Access
81-89 Access 1-9
90 Opening
91-99 Opening 1-9
[DC4] Represents the terminator
Example
Printer: L1-1234-03-LIBRARY WORD
HH:MM:SS-DD/MM
Computer: E01001 123403 [14]
7.13 Silent Knight FSK2 Protocol
The DRL2E will provide two possible outputs to the
computer, according to the value set under option A7.
When the option is programmed as “02”, the com-
puter output will be as follows:
FRRLssssAAAAAAYYZZss[DC4]
Where:
F FSK2 protocol 1 identifier
RR Receiver number
L Line number
s Spaces
AAAAAA Account number (if the account is 4 or 5
digits, the leading “A”s will be replaced by
spaces)
YY Event code
ZZ Zone/user number
[DC4] Represents the terminator
Possible events are as follows:
YT00 Battery Trouble
YR00 Battery Restore
AT00 System Trouble AC
DOZZ Access left open ID ZZ
DFZZ Access forced ID ZZ
DSZZ Access Station ID ZZ
AJ00 System Restore AC
LT0Z Trouble phone line #0Z
Restore phone line 0Z
Expand trouble device ID z
Expand restore device ID z
ETZZ Expand trouble station ID ZZ (ZZ=17-31)
ERZZ Expand restore station ID ZZ (ZZ=17-31)
RP00 Automatic test
RXZZ Manual test zone ZZ
CA Automatic closing
OA Automatic opening
CLZZ Normal closing ID ZZ
OPZZ Normal opening ID ZZ
CFZZ Forced closing ID ZZ
ORZZ Forced opening ID ZZ
Supervised closing ID ZZ
OTZZ Supervised opening ZZ
CG0a Closing area 0a
OG0a Opening area 0a
DRZZ Access granted ID ZZ
When the option is programmed as “01”, the com-
puter output will be as follows:
CRRLssssAAAAAAXYZZss[DC4]
Where:
C FSK2 protocol 2 identifier
RR Receiver number
L Line number
s Spaces
AAAAAA Account number (if the account is 4 or 5
digits, the leading “A”s will be replaced by
spaces)
XEvent code
Y Condition code
ZZ Zone/user number
[DC4] Represents the terminator
Possible events are as follows:
B600 Battery Trouble
BE00 Battery Restore
C600 System Trouble AC
CE00 System Restore AC
D60z Trouble phone line #0z
DE0z Restore phone line 0z
E60z Expand trouble device ID z
EE0z Expand restore device ID z