Compact Operating Instructions – DOP11C
4
Connecting the operator panel
Installation
Potential shift
Ethernet connec-
tion
Connecting DOP11C to a PC for programming and remote maintenance via Ethernet
and TCP/IP.
Cable specification Use a standard shielded Ethernet cable with shielded RJ45 connectors and cables ac-
cording to the CAT5 specification. The maximum cable length is 100 m.
For example, the following cable is suitable:
UNITRONIC
®
LAN UTP BS flexible 4 x 2 x 26 AWG by Lappkabel
Ethernet connec-
tions of DOP11C-
120 and -150
The units DOP11C-120 and -150 are equipped with 2 Ethernet connections.
Note: The Ethernet connections cannot be used as a switch (with the same IP address).
Used the Ethernet connections independently (only one or both at one time) in order
to connect the operator panel to other devices (inverters, controller).
Assign one IP address from your local network (IP address range) to each Ethernet
connection.
NOTICE
There must not be any potential shift between the units connected to RS485. Take
suitable measures to avoid potential shift, for example, by connecting the unit grounds
(GND) with a separate cable, connecting the voltage supply (24 V) etc.
8997845259
DOP11C
LAN
Switch /
Hub
Uplink