Specifications

64
ALL THINGS BACNET
CONFIGURATION OBJECTS
Object
Identifier
Name
Description
10020
Data Acquisition Tick
Internal sample count (gets cleared every minute): may be used to
determine if sample read is a newer sample than last read.
10140
Clear Accumulated
Measurements
Writing 1234 to the present value will reset all the accumulator
objects (kWh, kVAh, kVARh)
10190
Communications protocol
Used to change between BACnet and Modbus communications
protocols.
12003
CT3 Phase Shift
CT3 phase shift (degrees)
12011
CT1 Value
CT1 Value
12012
CT2 Value
CT2 Value
12013
CT3 Value
CT3 Value
12030
CT Pulse Scalar
Changes the scaling of the output pulses
12040
Demand Window
Demand window size in minutes; default is 15 min
12050
Volts Multiplier
Multiply volts values by this scalar. For use with stepdown
transformer. Affects all parameters that use volts.
12061
CT1 Amps Multiplier
Multiply CT1 amps values by this scalar. For use with stepdown
transformer. Affects all parameters that use amps.
12062
CT2 Amps Multiplier
Multiply CT2 amps values by this scalar. For use with stepdown
transformer. Affects all parameters that use amps.
12063
CT3 Amps Multiplier
Multiply CT3 amps values by this scalar. For use with stepdown
transformer. Affects all parameters that use amps.
12080
Service Type
A value of 1 configures the meter for Delta.
A value of 0 configures the meter for Wye.
12090
Line Frequency
Line frequency setting for metering. 50 = 50 Hz, 60 = 60 Hz
12130
CT Type All
Writes same type for all CTs: 1=MilliVolt, 2=Rogowski