Specifications

37
ENTERING WIRING INFORMATION FOR AN ELEMENT
Begin setup by entering an amount of time (1-60 minutes) into the Demand Window and selecting a
Line Frequency from the drop-down list.
Use the following steps:
1) Select WYE or DELTA as the wiring connection.
A WYE connection automatically displays all three CTs. Any changes made to CT1 also apply to
CT2 and CT3.
Wye Wiring Connection
A DELTA connection displays only the two available CTs. Any changes made to CT1 also apply to
CT3.
Delta Wiring Connection
2) Depending on the wiring connection, make changes to CT1, CT2, and/or CT3.
*CT PhaseSelect which phase to monitor
CT TypeUse the drop-down list to select the type of CT attached to the Power Patrol.
*CT AmpsEnter the amperage rating.
*CT Phase ShiftEnter in degrees the phase shift of the CT. The default is 1.1.
*Apply to MilliVolt CT not Rogowski Coils