Specifications
29
CONNECTING PORTS
Once your communication mode is selected, click Connect to establish a connection between the
computer and the Power Patrol meter.
When the Power Patrol meter is in the process of connecting to the computer, the
Communication Status LED flashes briefly followed by a solid green.
If the Power Patrol meter cannot connect to the computer, the Communication Status LED
flashes red and returns to a solid green. Change the HeadStart hardware settings and click
Connect again.
HeadStart fills the Device Info fields when the computer communicates with the Power Patrol.
Power Patrol meter installation can be verified using the HeadStart software. Refer to Using HeadStart
Software further in this section for more information.
Establishing Communication Protocol
The Power Patrol meter communicates using the BACnet MS/TP or Modbus RTU protocols via the
RS-485/Ethernet interfaces. To establish communication with a RS-485, the settings must meet the
following requirements:
The Modbus/BACnet address on the Power Patrol and in the HeadStart software must be set to
the same value. Refer to Using the HeadStart Software to set the address on the
Communications tab and establish a connection.
The Power Patrol meter default serial parameters are:
Parameter
Defaults
Modbus
Settings
BACnet
Settings
Baud
9600
76800
Data bits
8
8
Parity
None
None
Stop Bit
1
1
Table III-3: Serial Communication Settings
The supported baud rates include 9600, 19200, 38400, 57600 (Modbus only), 76800, and 115200
(Modbus only).
NOTE: The baud rate on the user interface (HeadStart) must match the Power Patrol setting. If these
settings differ, the Power Patrol cannot communicate.