Product specifications

Phone: 800-257-3872 • Fax: 978-264-0292 • setra.com ©2014 Setra Systems, Inc. All rights reserved. The Setra Systems name and logo are registered trademarks of Setra Systems, Inc.
DIFFERENTIAL PRESSURE
66
DIMENSIONS
Sure-Set
Split Core Current Switch

Sure-Set Scaled in Motor Hp, Allowing User
to Preset Unit Prior to Installation
9 Motor HP Settings Per Model


Snap-on Power Relay Option

 -
No Personal Protective Equipment Required
No Live Calibration Required - Save Time
and Labor

Switchover Current
APPLICATIONS

Refrigeration
Pumps
Industrial Motors

Lighting
Heaters
2.70
68.6
2.56
65
1.08
27.4
2.70
68.6
2.56
65
1.73
44
in.
mm
Model
SSC-2H
SSC-4H
Shown with
Optional CCRXX
Snap-on Power
Relay
Patent Pending
DESCRIPTION
The Sure-Set Model SSC Split Core Current Switch provides a unique
approach to calibration and installing current sensors that eliminates
-
curate method of setting the proper current set point for the appli-

the Sure-Set Current Switch allows installation without the need for

the 9 position Sure-Set Selector and the scale rated in motor HP, the
installer simply sets the selector to the rated motor HP prior to open-
ing the electrical enclosure. The installer powers down the electrical
enclosure, snaps the Sure-Set onto the sensed conductor, connects
the signal leads, closes the enclosure and powers up the system. No
further calibration is required! In fact, the engineer or installer can pre-
set all the Sure Set current switches used in a system prior to arriving
at the job site, making the on-site install time for the current switches
even shorter.
Oered with 9 HP settings per range, the Sure Set has the derating

set the Sure-Set 9 position selector switch to the rated motor HP and
install. The Sure-Set, like other members of Setras Current Switch fam-


is CE and RoHS compliant.