Product specifications
©2014 Setra Systems, Inc. All rights reserved. The Setra Systems name and logo are registered trademarks of Setra Systems, Inc. Phone: 800-257-3872 • Fax: 978-264-0292 • setra.com
DIFFERENTIAL PRESSURE
63
CURRENT SENSORS
Model CSC Series
Split Core Current Switches
Model Description
CSCGA2125NN
Model CSC, Adjustable Setpoint, with LED, 1.25 A Setpoint, No Snap-on Power Relay
CSCGA2125R1
Model CSC, Adjustable Setpoint, with LED, 1.25 A Setpoint, with Snap-on Power
Relay
MODEL CSCGFN015NN
CSCGFN150NN
CSCGA2125NN CSCGFN150R1
w/snap-on relay
CSCGA2125R1
w/snap-on relay
Amperage Range 0.15 to 200 A/ 1.5 to 200 A 1.25 to 135 A 1.5 to 200 A 1.25 to 135 A
Continuous Operating Current 200 A, 600 V AC/
200 A, 600 V AC
135 A, 600 V AC 200 A, 600 V AC 135 A, 600 V AC
Switch Setpoint Fixed Adjustable Fixed Adjustable
Output Relay No No SPST. NO 10 A @ 260 V AC, 5 A
@ 30 VDC
SPST. NO. 10 A @ 260 V AC,
5 A @ 30 V DC
Actuation Coil No No 24 V AC/DC 24 V AC/DC
Switch LED Indication No Yes No Yes
Relay LED Indication No No Yes Yes
Trip Setpoint Value 0.15 A/1.5 A 1.25 to 135 A 1.5 A 1.25 to 135 A
Current Switching Mode Under Current Sensing Over/Under Current Sensing Under Current Sensing Over/Under Current Sensing
Dimensions 2.7 x 2.56 x 1.08 in.
(69 x 65 x 27 mm)
2.7 x 2.56 x 1.08 in.
(69 x 65 x 27 mm)
2.7 x 2.56 x 1.73 in.
(69 x 65 x 44 mm)
2.7 x 2.56 x 1.73 in.
(69 x 65 x 44 mm)
Aperture (Sensing Hole Size) 0.72 x 0.78 in. (18 x 20 mm)
Sensor Supply Voltage Induced from power conductor cable
Status Output Switch normally open
Switch Load Capacity 1 A @ 30 V AC/DC max.
Isolation Voltage 600 V AC rms
Temperature Range 5 to 140°F (-15 to 60°C)
Frequency Range 50/60 Hz
Humidity Range 0 to 95% non-condensing
Agency Approvals CE Compliant, RoHS Compliant, c-UL Listed: 508, IND. Cont. EQ: E317719