Product specifications

©2014 Setra Systems, Inc. All rights reserved. The Setra Systems name and logo are registered trademarks of Setra Systems, Inc. Phone: 800-257-3872 • Fax: 978-264-0292 • setra.com
DIFFERENTIAL PRESSURE
57
*IEEE C57.13 Certication available upon request
Split Core Standard CT
Current Transformers
DESCRIPTION
Split Core Standard CTs provide linear output voltage
that is directly proportional to the input current. These
current transformers are safely and easily installed over
existing electrical power lines without disconnecting
the lines or interrupting service.
Setras energy monitoring components are used for a
variety of applications including building automation,
tenant submetering, performance verication, energy
management, and new technology assessment.
SPECIFICATIONS
100A 200A 400A 600A
Window Size
1.25” (3.20 cm)
Current Range 5-130A AC 4-260A AC 8-520A AC 12-780A AC
Output 333 mV @ rated current
Ratio Error* <1% at rated current (typical)
Phase Error <2
o
at rated current (typical)
Electrical
Wire Polarity White = Hi, positive (+) Black + Low, negative (-)
Frequency Range 50 to 400 Hz
Mechanical
Case Material Epoxy Encapsulated Housing
Leads 2.7 M (8’), twisted pair, 20 AWG
Operating Temp. Maximum 105
o
C (220
o
F)
Safety
Working Voltage 600 VAC, Category III
Dielectric Strength 5000 VAC around case, 600V rated leads
Certications UL STD 61010-1, EN 60044-1:1999
Certied to: CAN/CSA STD 22.2 NO. 61010-1
Dimensions
A B C D E
8.26 cm
(3.25”)
8.51 cm
(3.35”)
2.54 cm
(1.00”)
3.18 cm
(1.25”)
3.18 cm
(1.25”)


C T
Name Amps
SCS Split Core Standard 100 100 Amps
200 200 Amps
400 400 Amps
600 600 Amps
S C S