Product specifications

Phone: 800-257-3872 • Fax: 978-264-0292 • setra.com ©2014 Setra Systems, Inc. All rights reserved. The Setra Systems name and logo are registered trademarks of Setra Systems, Inc.
DIFFERENTIAL PRESSURE
56
POWER MONITORING
Patrol Flex
Rogowski Coil
DESCRIPTION
The Setra Patrol Flex is an AC current probe utilizing the Rogowski prin-
ciple. The exible and lightweight measuring head allows quick and easy
installation in hard to reach areas, without batteries or an external power
source.
Setra Patrol Flex is available as a 3-pack, perfect for use with 3-phase power
applications. The Flex clamp ts around bus bars and large or hard-to-
reach conductors.
SPECIFICATIONS
General Specications Specications Safety Specications
Probe and Cable
Material
TPE rubber, reinforced insulation
UL94 V-0, Colour: RED Munsell 7.5
R 1/14
Current Range 12” - 0-1500A
24” - 0-3000A
36” - 0-6000A
Safety
Standards
-BS EN 61010-1 2001
- BS EN 61010-2-032 2002
-BS EN 61010-031 2002, 1000 VRMS,
Category III, Pollution Degree 2
-Use of the probe on uninsulated
conductors is limited to 1000 V
ACRMS or DC and frequencies below
1 kHz.
- Please note that this probe is
designed to work with Fluke 435, if
used with other products safety rat-
ing for the output to earth is limited
to 600V ACRMS or DC.
Couplings Material Polypropylene, UL94 V-0 Voltage Output
(@1000 ARMS, 50 Hz)
85 mV
Probe Cable Length 610 mm Accuracy ± 1% of reading
(@ 25°C, 50 Hz)
Probe Cable Diameter 12.4 mm Linearity (10% to
100% of range)
± 0.2% of reading
Probe Cable Bend
Radius
40 mm Noise (10 Hz - 7 Hz) 1.0 mV ACRMS
Output Cable Length 2.5 meters RG58 Output Impedance 82 Ω min
Output Connector Unterminated Load Impedance 50 kΩ
Operating Range -20° to +90° C Internal Resistance
per 100 mm probe
length
10.5Ω ± 5%
Storage Temperature -40° to +105° C Bandwidth (-3dB) 10 Hz to 7 kHz
Operating Humidity 15% to 85% (non condensing) Phase Error (45-65 Hz) ±1°
Degree of Protection
(Probe)
IP41 Position Sensitivity ± 2% of reading max.
Temperature Coef-
cient
± 0.08% max of reading
per °C
Working Voltage (see
Safety Standards
section)
1000 V AC RMS or
DC (head) 30 V max.
(output)
ORDERING INFORMATION
C T P F
Name Probe Length
PF Patrol Flex 12 12”
24 24”
36 36”