Product specifications

©2013 Setra Systems, Inc. All rights reserved. The Setra Systems name and logo are registered trademarks of Setra Systems, Inc. Phone: 800-257-3872 • Fax: 978-264-0292 • www.setra.com
SPECIFICATIONS
Technical Communications
Service Type Single Phase, Three Phase-Four Wire (WYE), Three Phase-Three Wire (Delta) Direct BACnet IP, BACnet MS/TP, Modbus TCP, Modbus RTU
Power From L1 Phase to L2 Phase. 80-600VAC CAT III 50/60Hz, 70 mA Max. Non-
user replaceable .5 Amp internal fuse protection
Max Distance 1200 meters with data rate of 100K bits.second of less
Voltage Channels 80-346 Volts AC Line-to-Neutral, 600V Phase-to-Phase, CAT III Baud Rate 9600 (Modbus default), 19200, 38400, 57600, 76800
(BACnet default), 11200
Current Channels 3 Channels, 0.67 VAC max, 333 mV CTs, 0-4,700 Amps depending on CT Data Bits 8
Maximum Current
Input
200% of current transducer rating (mV CTs)
Measure up to 5000A Patrol Flex
Parity None, Even, Odd
Measurement
Type
True RMS using high-speed digital signal processing (DSP) Stop Bit 2,1
Line Frequency 50/60 Data Formats Modbus or BACnet
Waveform
Sampling
12 kHz
Mechanical
Parameter
Update Rate
.5 seconds Operating Temperature -7
o
to 60
o
C (-20
o
to 140
o
F)
Measurements Volts, Amps, kW, kWh, kVAR, kVARh, kVA, aPF, dPF (Partial List) Humidity 5% to 95% non-condensing
Accuracy 0.2% (<0.1% typical) ANSI C12.20-2010 Class 0.2 Enclosure ABS Plastic, 94-V0 ammability rating
Resolution 0.01 Amp, 0.1 Volt, 0.01 watt, 0.01 VAR, 0.01 VA, 0.01 Power Factor
depending on scalar setting
Weight 340 g (12 ounces, exclusive of CTs
LED Indicators Bi-color LEDs (red and green): 1 LED to indicate communication, 2 LEDs for
correct CT-to-phase installation (per meter element), 1 LED for pulse
Dimensions 23.0 x 9.0 x 4.0 cm, (9.0” x 3.5” x 1.5”)
Pulse Output Open Collector, 5mA max current, 30V max open voltage
Safety
Power Patrol Serial and
Ethernet
UL Listed and CE Mark,
Conforms to UL Std 61010-1
Certied to CSA Std C22.2 No. 61010-1
Modbus Register/BACnet Object Descriptions (Partial List)
System True Energy (kWh) Individual Phase to Phase Voltages
Instantaneous Total True Power (kW) Line Frequency (Hz)
Peak Demand (Adjustable Window) (kW) Individual Phases True Energy (kWh)
Maximum Instantaneous Power (kW) Individual Phases True Power (kW)
System Reactive Energy (kVARh) Individual Phases Reactive Energy (kVARh)
System Apparent Energy (kVAh) Individual Phases Reactive Power (kVAR)
System Apparent Power (kVA) Individual Phases Apparent Energy (kVAh)
System Displacement Power Factor (dPF) Individual Phases Apparent Power (kVA)
System Apparent Power Factor (aPF) Individual Phases Apparent Power Factor (aPF)
Average Current (Amps) Individual Phases Displacement Power Factor (dPF)
Average Line to Line Voltage (Volts) Individual Phases Current (Amps)
Average Line to Neutral Voltage (Volts) Individual Phases Line to Neutral Voltages (Volts)
Multiple Meters External Data Synchronization Individual Phases Line to Line Voltages (Volts)
Power Patrol
Advanced Power Meter
S P P
Ordering Information
for Setra Power Patrol
SPP - Setra Power Patrol
Communication Port
E - Ethernet & Serial
S - Serial Only (RS-485)
Display
D - Display
N - No Display
Setra P/N Description
900900-G USB Communication Cable, Type A to B, Power Patrol
900901-G USB Flash Drive, HeadStart Software, Power Patrol
Communication
Accessories
(Cable and software required for meter setup)