Product specifications

Phone: 800-257-3872 • Fax: 978-264-0292 • setra.com ©2014 Setra Systems, Inc. All rights reserved. The Setra Systems name and logo are registered trademarks of Setra Systems, Inc.
DIFFERENTIAL PRESSURE
44
Model SRCM
Room Pressure and Condition Monitor
DIMENSIONS
cm
in.
18.92
7.45
14.84
5.84
0.95
0.38
1.49
0.59
7.03
2.77
13.15
5.18
5.08
2.00

ANALOG (ANL) OUTPUT
COM COM
mA Current Output (4-20 mA)
Vdc Voltage Output (0-5 Vdc, 0-10 Vdc)
INPUTS (wired to door N.O. contact)
COM COM Door
DI Digital Input
COM COM Analog Input2
IN2 Analog Input2 (0-5, 0-10Vdc)
+15 15 Vdc
COM COM Analog Input1
IN1 Analog Input1 (0-5, 0-10Vdc)
+15 15 Vdc
Earth Ground
L1 24 Vac
L2 24 Vac
HIGH or room pressure tubing
contacts here
LOW or reference pressure tubing
connects here
POWER
RELAY
COM COM
+15 +15 Vdc
NO Normally Open
RC Relay COM
NC Normally Closed
COM
B (+)
A (-)
GND
REAR VIEW
ROOM PRESSURE MONITORS
SPECIFICATIONS
Performance Data Environmental Data Electrical Data (Voltage)
Code F Code H
Operating
3
Temperature
°F (°C)
32 to + 120 (0 to +50) Circuit 3-Wire (Exc, Out, Com),
Accuracy RSS
1
(at constant temp) ±0.25% FS ±0.5%
Storage Temperature °F (°C) -20 to +160 (-30 to +70) Output
4
0 to 5 VDC, 0 to 10 VDC
Non-Linearity (BFSL based) ±0.24% ±0.49%
Operating Humidity 5 to 95% RH (non-condensing) Excitation 18-32 VAC, 50-60 HZ
Hysteresis ±0.05% ±0.05%
Physical Description
Power Consumption 10 W max., 3 W typ.
Non-Repeatability ±0.05% ±0.05%
Case Fire Retardant Plastic UL94 V-0 Alarm Output SPDT Relay: 0.6A @ 120 VAC, 2A @ 30 VDC
Zero/Span Tolerance ±0.05% FS ±0.05% FS
Dimensions 5.84”H x 7.45”W x 0.38”D (14.84 x 18.92 x 0.95 cm)
Electrical Data (Current)
Pressure Media
Electrical Connection Removable Terminal Block Circuit 2-Wire
Air or Non-Conductive, Non-Explosive Gases.
Pressure Fittings Barbed Fittings for 1/4” O.D. Tubing Output 4 to 20 mA
Certications
Weight (approx.) 1 lb. 3.2 ounces (554 grams) External Load 0 to 510 ohms
CE
Electro-Magnetic Compatibility
Directive 2004/108/EC
Low-Voltage Directive 2006/95/EC
RoHS Directive 2011/65/EC
Mounting Mounts to a triple gang double-deep electrical box Excitation 18-32 VAC
Communications Option
Thermal Eects
2
CSA
CAN/CSA - C22.2 No. 61010-1-04
ANSI/UL 61010-1, 2nd Edition
BACnet® MS/TP ASC Compensated Range °F (°C) ±0.03% FSI (±0.05% FS)
1
RSS of Non-Linearity, Hysteresis, and Non-Repeatability.
2
Units calibrated at nominal 70˚F. Maximum thermal error computed from this datum.
3
Operating Temperature limits of the electronics only.
4
Calibrated into a 50K ohm load, operable into a 5000 ohm load or greater.
Specications subject to change without notice.
Display Overpressure ±1 PSI (15” W.C. for ≤ 0.10” W.C. F.S.)
LCD 4.3” TFT, 480 x 272, Dimmable