Product specifications
Phone: 800-257-3872 • Fax: 978-264-0292 • setra.com ©2014 Setra Systems, Inc. All rights reserved. The Setra Systems name and logo are registered trademarks of Setra Systems, Inc.
DIFFERENTIAL PRESSURE
36
Model MRMS
Multi-Room Monitoring Station
■  Remotely Monitor up to 8 Rooms
■ Auto-Discover
■ 
■  Display Room Status and Room Condition
■ 
■ Easy Installation
■  Reduce Total Installation Cost
■ 
■ 
■  Meets CE Conformance Standards 
APPLICATIONS
■  Nurses Station
■  Surgical Suites
■  Intensive Care Isolation Rooms
■ Pharmacology
■  Research Laboratories
■  Pharmaceutical Manufacturing
■   Clean Rooms
■  
■   
■ Organic Laboratory
DESCRIPTION
for installation in a central location, such as a nurses 
station or main control room. It is designed to be ush 
mounted to provide remote viewing and alarm monitor-
ing for up to 8 rooms or critical spaces equipped with Se-
tra’s Pressure and Room Condition Monitors, such as the 
Model SRPM or SRCM. The built-in Auto-Discover feature 
will automatically search and connect to other SRPM and 
-
er setup parameters. A built-in audible and visual alarm 
and high denition color display alerts users to room sta-
tus and room condition, while allowing for easy alert of a 
change in room condition.
ROOM PRESSURE MONITORS
SPECIFICATIONS
Physical Description Environmental Data Electrical Data (Voltage)
Case Fire Retardant Plastic UL94V-0
Operating Temperature
3
 °F (°C)  32 to +120 (0 to +50) Power Input 18-32 VAC, 50-60Hz
Dimensions) 5.84”H x 7.45”W x 0.38”D
Storage Temperature °F (°C)  -20 to +160 (-30 to +170) Power Consumption 10W
Electrical Connection Removable Terminal Block
Operating Humidity 5 to 95% RH (Non-Condensing) Circuit 2-Wire (Exc, Com)
Weight 1 ib. 2 oz. (482 grams)
Communications Certications
Mounting
Standard Triple Gang Double-Deep-Electrical 
Box
BACnet® MS/TP ASC  CE Conforms to European Pressure Directive
Display Touchscreen LCD 4.3” TFT, 480 x 272
CSA C22.2 No. 61010-1-04