User guide
3
  location of zero adjustment.) For 0-5 VDC output units, the factory settings   
  are 0.0VDC (±50mV) for unidirectional pressure ranges and 2.5VDC (±50mV)   
  for bidirectional pressure ranges. Optional outputs are set at the same ±1%   
  factory setting.   
  4.2 Voltage Output Span Adjustment (Complete the zero adjustment 
before setting span.)
  Span or full scale output adjustments should only be performed by using an 
accurate pressure standard (electronic manometer, digital pressure gage, etc.), 
with at least comparable accuracy to the 265 transducer (<±1% FS). With full 
range pressure applied to the high pressure port (reference port open to atmo-
sphere), the span may be adjusted by turning the SPAN adjustment screw. (See 
Diagram 1 for location of the SPAN adjustment.) For 0-5 VDC output units, the 
factory settings are 5.0 VDC (±50mV) for unidirectional and bidirectional ranges.  
Optional outputs are set at the same ±1% factory setting. 
  4.3 Current Output Zero Adjustment
  While monitoring the current output between +EXC and OUT, and with both 
pressure ports open to atmosphere, the zero may be adjusted by turning the 
zero adjustment screw. (See Diagram 1 for location of zero adjustment.) The 
factory settings are 4mA (0.16mA) for unidirectional pressure ranges and 12mA 
(0.16mA) for bidirectional ranges.
  4.4 Current Output Span Adjustment
  Span or full scale output adjustments should only be performed by using an 
accurate pressure standard (electronic manometer, digital pressure gage, 
etc.) with at least comparable accuracy to the 265 transducer (<±1% FS). With 
full range pressure applied to the high pressure port (reference port open to 
atmosphere), the span may be adjusted by turning the SPAN adjustment screw.  
(See Diagram 1 for location of SPAN adjustment.) The factory settings are 20mA 
(0.16mA) for unidirectional and bidirectional pressure ranges.
  5.0 MODEL 265 PERFORMANCE SPECIFICATIONS
  Accuracy RSS
*
  ±1.0% FS  Thermal Effects
  (at constant temperature.)    Compensated Range °F(°C)  0 to +150 (-18 to +65)
  Non-Linearity, BFSL  ±0.98% FS   Zero/Span Shift %FS/°F(°C)  0.033 (0.06)
  Hysteresis  0.1% FS  Maximum Line Pressure  10 psi
  Non-Repeatability  0.05% FS  Overpressure  10 psi in positive or 
  *RSS of Non-Linearity, Non-Repeatability    negative direction
  and Hysteresis.    Warm-up Shift  ±0.1% FS total
  Position Effects
  (Unit is factory calibrated at 0g effect in the vertical position)
  Range  Zero Offset (%FS/G)
  0 to 1” WC  .22
  0 to 5” WC  .14
  0 to 30” WC  .06