Specifications

Advanced Operations 95
Installation and Operations Manual
Configuring Temperature Recovery Delta:
The Temperature Recovery Delta command allows configuration of the number of degrees of change
needed to recover from a temperature alarm.
To configure the temperature recovery delta:
At the Switched CDU: prompt, type set event temp tempdelta, followed by the sensor name, the
number of degrees for the recovery delta, and press Enter.
NOTE: The acceptable value range for the Recovery Delta field is 0-10 degrees for Celsius and 0-18 degrees for
Fahrenheit. The default value for the Recovery Delta field is 1 degree Celsius and 2 degrees Fahrenheit.
Example
The following command configures the recovery delta at 2 degrees Fahrenheit for temperature/humidity
sensor .A1:
Switched CDU: event temp tempdelta temp_humid_sensor_A1 2<Enter>
Enabling or Disabling the Humidity trap:
The Set Trap THS Humid command is used to enable or disable the Humidity trap.
To Enable or Disable the Humid trap:
At the Switched CDU: prompt, type set trap ths humid, followed by the sensor name and on or off.
Press Enter.
Example
The following command enables the Humidity trap for the first temperature-humidity sensor:
Switched CDU: set traps ths humid .a1 on<Enter>
Setting the Humidity sensor threshold limits:
The Set Trap THS Humidlow and Set Trap THS Humidhigh commands are used to set the lower and
upper threshold limits for the Humidity sensor.
To set the Humidity threshold limits:
At the Switched CDU: prompt, type set trap ths, humidlow or humidhigh, followed by the sensor
name and a value from 0 to 100 in percentage of relative humidity. Press Enter.
Example
The following command sets the first humidity sensor low threshold limit to 5:
Switched CDU: set trap ths humidlow .a1 5<Enter>