Specifications
90 Advanced Operations
Installation and Operations Manual
To display SNMP configuration information:
At the Switched CDU: prompt, type show snmp and press Enter.
Example
The following command displays the SNMP configuration information:
Switched CDU: show snmp<Enter>
SNMP Configuration
SNMPv2: Disabled
GET Community String: ABC
SET Community String: DEF
TRAP Community String: XYZ
SNMPv3: Enabled
V3 RW Username: RW_User
V3 RW Auth Type: None <password set>
V3 RW Privacy Type: None <password set>
V3 RO Username: RO_User
V3 RO Auth Type: None <password set>
V3 Trap Username <undefined>
Trap Destination 1 : 10.1.2.80
Trap Destination 2 : 10.1.6.52
Trap format : v3
IP Restrictions: No Restrictions
Error Trap Repeat Time : 60 seconds
SysName: Sentry3_524640
SysLocation: Test_Bed3
SysContact: Jim Davis
Command successful
SNMP Traps
The Switched CDU supports five types of SNMP traps. Traps are enabled at the Tower (T), Infeed (I),
outlet (O), Environmental Monitor (E) or sensor (S) level.
Trap Summary
Name Level(s) Description
Status T, I, O, E, S Operational status change
Change O Control status change
Load I Input load out of limit
Temp S Temperature is out of range
Humid S Relative Humidity is out of range
All traps include the location of the PT22 as defined with the Set Location command.