Specifications

Operations 79
Installation and Operations Manual
Adding an infeed to a UPS:
The Set UPS AddInfeed command adds a logical association of an infeed to a UPS.
To add an infeed to a UPS:
At the Switched CDU: prompt, type set ups addinfeed and press Enter.
At the prompt, enter the index number for the UPS record to be changed and press Enter.
At the prompt, type the absolute infeed ID of the desired infeed, and press Enter.
Example
The following command associates infeed .aa to UPS record at index number 1:
Switched CDU: set ups addinfeed<Enter>
UPS UPS Infeed
Index Type IDs
1 Liebert
2 MGE .AA
Select UPS(1-8): 1<Enter>
Infeed ID: .aa<Enter>
Removing an infeed from a UPS:
The Set UPS DelInfeed command removes a logical association of an infeed from a UPS.
To remove an infeed from a UPS:
At the Switched CDU: prompt, type set ups delinfeed and press Enter.
At the prompt, enter the index number for the UPS record to be changed and press Enter.
At the prompt, type the absolute infeed ID of the desired infeed, and press Enter.
Example
The following command removes the association of infeed .aa from UPS record at index number 2:
Switched CDU: set ups addinfeed<Enter>
UPS UPS Infeed
Index Type IDs
1 Liebert .AA
2 MGE .AA
Select UPS(1-8): 2<Enter>
Infeed ID: .aa<Enter>
Displaying UPS configuration:
The Show UPS command displays information about all UPS devices.
UPS Type and Host/IP address
UPS SNMP port and community string
SNMP Objects OID values and expected return values
To display UPS configuration information:
At the Switched CDU: prompt, type show ups and press Enter.
Example
The following command displays UPS configuration information:
Switched CDU: show ups<Enter>
1 Type: Liebert
Host/IP: DC1Liebert1
Voltage Polling: ON
SNMP Configuration
Community String: public
SNMP Port: 162
SNMP Objects/Expected Values
Voltage: .1.3.6.1.2.1.33.1.4.4.1.2.1
Utility Status: .1.3.6.1.2.1.33.1.4.1.0
On Battery: 0x5
On Utility: 0x3
More (Y/es N/o):