Specifications

64 Operations
Installation and Operations Manual
Setting the outlet sequence order:
The CDU lets you configure the power-on sequence of outlets.
The Normal option powers-on outlets in ascending numeric order by outlet number, for example, from
outlet 1-8. The Reversed option powers on outlets in descending order by outlet number; for example,
from outlet 8-1.
The Reversed option is useful when the CDU is mounted with inverted orientation and the last outlet
(in this example, outlet 8) is in the first position.
At the Switched CDU: prompt, type set option outletsequence, followed by normal or reversed, and
press Enter.
Setting the temperature scale:
The Set Option TempScale command sets the temperature scale that the PT22 will report in.
To set the temperature scale:
At the Switched CDU: prompt, type set option tempscale, followed by celsius or fahrenheit and press
Enter.
Configuring the Command Line Interface (CLI) session timeout:
The Set Option CLI Timeout command configures the CLI session timeout in minutes.
The valid timeout range is 1 to 1440 minutes (24 hours). The default session timeout is 5 minutes.
To configure the CLI Session Timeout:
At the Switched CDU: prompt, type set option clitimeout, followed by the session timeout (in
minutes), and press Enter.
Example:
The following command sets the CLI session timeout to 15 minutes:
Switched CDU: set option clitimeout 15<Enter>
Configuring the web session (Web Interface) timeout:
The Set Option Web Timeout command configures the Web session timeout in minutes.
The valid timeout range is 1 to 1440 minutes (24 hours). The default session timeout is 5 minutes.
To configure the web session timeout:
At the Switched CDU: prompt, type set option webtimeout, followed by the session timeout (in
minutes), and press Enter.
Example:
The following command sets the web session (Web Interface) timeout to 10 minutes:
Switched CDU: set option webtimeout 10<Enter>