Displaying outlet information:
The Show Outlets command displays information about all outlets. This information includes:
Sequencing and reboot timer values
Descriptive outlet name, if applicable
Outlet wakeup state and Post-On settings
To display outlet information:
At the Switched CDU: prompt, type show outlets and press Enter.
Example
The following command displays all outlet information:
Switched CDU: show outlets<Enter>
Outlet Outlet Wakeup Post-On
ID Name State Delay (seconds)
.A1 DataServer_1 On 0
.A2 WebServer_1 On 0
.A3 FileServer_1 On 0
.A4 TowerA_Outlet4 On 0
.A5 TowerA_Outlet5 On 90
.A6 TowerA_Outlet6 On 0
.A7 TowerA_Outlet7 On 0
.A8 TowerA_Outlet8 On 0
.A9 TowerA_Outlet9 On 0
.A10 TowerA_Outlet10 On 0
.A11 TowerA_Outlet11 On 0
.A12 TowerA_Outlet12 On 0
.A13 TowerA_Outlet13 On 0
.A14 TowerA_Outlet14 On 0
.A15 TowerA_Outlet15 On 0
.A16 TowerA_Outlet16 On 0
More (Y/es N/o):
Outlet Options:
Sequence Interval: 2 seconds
Reboot Delay: 15 seconds
Input Feed Administration
Creating a descriptive infeed name:
The Set Infeed Name command assigns a descriptive name to an infeed. This descriptive name is
displayed when the Show Traps command is issued.
To create a infeed name:
At the Switched CDU: prompt, type set infeed name followed by the absolute infeed name, then a
descriptive name of up to 24 alphanumeric and other typed characters - (ASCII 33 to 126 decimal) are
allowed; spaces are not allowed. Press Enter.
Example
The following command adds the descriptive name HQ_1_Infeed_A to the infeed on the PT22:
Switched CDU: set infeed name .aa HQ_1_Infeed_A<Enter>
Setting the infeed operational voltage
The Set Infeed Voltage command is use to edit the input operational voltage.
To set the infeed operational voltage:
At the Switched CDU: prompt, type set infeed voltage, followed by the absolute infeed name, and a
value from 0 to 480. Press Enter.
Example
The following commands sets the operational voltage for input .AA to 100V:
Switched CDU: set infeed voltage .aa 100<Enter>