Specifications
Operations 21
Installation and Operations Manual
Outlet State/Control State Field Values
Outlet State Control State Description
On On Outlet is on
Off Off Outlet is off
Off Pend On Outlet is off and about to turn on in response to a sequence timer
Off Reboot Outlet is off and a Reboot action has been initiated
On Idle On A restart has occurred: Last Control State has been maintained
Off Idle Off A restart has occurred: Last Control State has been maintained
On Wake On A power-loss has occurred: Wakeup State has been applied
Off Wake Off A power-loss has occurred: Wakeup State has been applied
On/Wait Off Outlet state in transition: Re-query of outlet status required
Off/Wait On Outlet state in transition: Re-query of outlet status required
On/Error varies Error State: Outlet should be off, but current is sensed at the outlet
Off/Error varies Error State: Outlet should be on, but no current is sensed at the outlet
Off/Fuse On Outlet should be on, but a blown fuse has been detected
No Comm varies Communication to the outlet has been lost*
* Control state will be applied when communication is re-established.
Power Monitoring
Input Feeds
The Input Feeds page displays:
The absolute and descriptive names of the infeed
Infeed status
Input/branch phase load in amperes
Input Voltage
Calculated power usage in Watts.
Monitor pages (like the Input Feeds page) refresh occasionally to reflect current PT22 status.
System
The System page displays:
Calculated power usage for all
infeeds in Watts
Configured total system area in square feet.
Calculated power usage in Watts/square foot.
Monitor pages (like the System page) refresh occasionally to reflect current PT22 status.
UPS
The UPS page displays the following information for each UPS device associated with the PT22 unit:
Status
Voltage
Hostname/IP address
Monitor pages (like the UPS page) refresh occasionally to reflect current PT22 status.
.
Environmental Monitoring
Sensors
The Sensors page displays:
Temperature/humidity sensor’s absolute and descriptive names
Temperature/humidity sensor readings in degrees Celsius and percentage of relative humidity
Monitor pages (like the Sensors page) refresh occasionally to reflect current PT22 status.