Specifications

Operations 15
Installation and Operations Manual
Interfaces
The PT22 unit has two interfaces: the Web interface accessed via the HTTP-enabled Ethernet
connections, and the Command Line Interface (CLI) for serial and Telnet connections.
Outlet Naming and Grouping
For commands requiring an outlet name, you can specify the outlet command in one of two ways: a
predefined absolute name or a descriptive name assigned by an administrator.
For units with multiple infeed connectors, absolute names are specified by a period (.) followed by the
tower letter, the infeed letter, and outlet number.
Example: The absolute name for outlet 8 on the B infeed of tower A is .AB8.
Outlets can also be included in one or more named groups of outlets, allowing you to issue a command
that affects all outlets in a named group.
Usernames and Passwords
The PT22 unit has one predefined administrative user account (username/password: admn/admn), and
supports a maximum of 112 defined user accounts.
NOTE: For security, Server Technology recommends first creating a new administrative user account with administrative
rights before removing the default account admn.
Only an administrative-level user can perform operations such as creating/removing user accounts and
command privileges, changing passwords, and displaying user information. An administrator can also
view the status of all sensors and power inputs.
Usernames can contain from 1-16 characters and are not case sensitive; spaces are not allowed.
Passwords can contain up to 16 characters, and are case sensitive.