Specifications
Advanced Operations 125
Installation and Operations Manual
Enabling and Setting up Remote Shutdown Support
Remote Shutdown Command Summary
Command Description
Set Outlet Host Sets the target server Host IP address or hostname
Set Outlet Shutdown Enables or Disables Remote Shutdown
Set Outlet Shutdown Delay Sets the outlet Remote Shutdown delay
Set Outlet Script Enables or disables shutdown script delays
Set Outlet Script Delay Sets the outlet shutdown script delay
Show Shutdown Displays Remote Shutdown configuration information
Enabling or disabling Remote Shutdown support:
The Set Outlet Shutdown command enables or disables Remote Shutdown support for an outlet.
To enable or disable Remote Shutdown support:
At the Switched CDU: prompt, type set outlet shutdown, followed by yes or no, and the outlet ID.
Press Enter.
Example
The following command enables Remote Shutdown from outlet .a1:
Switched CDU: set outlet shutdown yes .a1<Enter>
Setting the Remote Shutdown delay:
The Set Outlet Shutdown Delay command sets the Remote Shutdown delay for an outlet.
To set the Remote Shutdown delay:
At the Switched CDU: prompt, type set outlet shutdown delay, followed by the outlet ID, and a value
from 30 to 900 (in seconds). Press Enter.
Example
The following command sets the Remote Shutdown delay for outlet .a2 to 120 seconds:
Switched CDU: set outlet shutdown delay .a2 120<Enter>
Setting the outlet host address:
The Set Outlet Host command set the IP address or hostname for an outlet. Hostnames can be up to 60
characters long.
To set the outlet host address:
At the Switched CDU: prompt, type set outlet host, followed by the outlet ID, and the IP address or
hostname. Press Enter.
Example
The following command set the hostname for outlet .a1 to ‘Windows2003’:
Switched CDU: set outlet host .a1 Windows2003<Enter>
Enabling or disabling shutdown script support:
The Set Outlet Script command enables or disables shutdown script support for an outlet.
To enable or disable shutdown script support:
At the Switched CDU: prompt, type set outlet script, followed by yes or no, and the outlet ID. Press
Enter.
Example
The following command enables Remote Shutdown from outlet .a1:
Switched CDU: set outlet script yes .a1<Enter>