User manual
User Manual SCA-SS-70-10
4.6.1 Setting of the Jumpers
Mode Current Set Value via
Analog
Position 0 – 10 A 0 – 5 A 3 – 7 A 5 – 10 A
Offset -
pot Connector
Note: Advanced information’s about the jumpers refer chapter 5.3.
4.6.2 Adjustment procedure for Analog Position mode
1. Potentiometer pre setting refer chapter 5.2.
2. Choose the maximum set value (e.g. 10 V). Turn the potentiometer n max, until the
desired moving angle is reached with unloaded motor.
3. Adjust the current limiter to a value requested by you with the I max potentiometer.
It is of major importance that this value is lower than the maximum admissible
constant current (see motor data sheet). To measure the motor current use a
current probe in one of the motor cables with an oscilloscope or a multimeter, or
the Monitor I output.
4. Slowly raise the value of the Gain potentiometer. If the motor begins to work
unsteadily, to vibrate or to cause excessive noise, carefully lower the gain factor
again, until the instability symptoms have disappeared for all load selections
5. Set the set value to zero and adjust the Offset potentiometer, to the standstill of the
motor.
Note:
The inputs Disable Rev and Disable Fwd can be used as limit switches to protect
the feedback system.