User Manual SCA-SS-70-10
4.3.1 Setting of the Jumpers
Mode Current Set Value via
Torque
Control 0 – 10 A 0 – 5 A 3 – 7 A 5 – 10 A
Offset -
pot Connector
Note: Advanced information’s about the jumpers refer chapter 5.3.
4.3.2 Adjustment procedure for Torque mode
1. Potentiometer pre setting refer chapter 5.2.
2. Adjust the current limiter to a value requested by you with the I max potentiometer. It
is of major importance that this value is lower than the maximum admissible constant
current (see motor data sheet). To measure the motor current use a current probe in
one of the motor cables with an oscilloscope or a multimeter, or the Monitor I output.
3. Choose the maximum set value (e.g. 10 V). Turn the potentiometer n max, until the
desired maximum current is reached.
4. Set the set value to zero and adjust the Offset potentiometer, to the standstill of the
motor.