4. Wiring
According to the safety directives, a correct cable selection is mandatory. Regular
inspection is advisable. Damaged, burned or kinked items have immediately to be
exchanged.
Power (Vcc - Power GND)
Normally no shielding required.
When connecting several amplifiers to the same supply pack, use star point
wiring.
Motor Wiring (> 30 cm)
Only shielded cables are recommended.
Connect the shield to the ground lug of the servo amplifier.
A separate cable has to be used.
Choke modules are useful to reduce PWM-pulses.
Connection to encoder (> 30 cm)
Only shielded cables are recommended.
Connect the shield to the controller.
A separate cable has to be used.
Analog Signals (+Set value, -Set value, Monitor I, Monitor n, +Tacho, -Tacho)
In most cases no shielding required. This may be different for low level signals or
in an environment with strong magnetic interference.
Connect the shield on either end of the cable. For 50/60 Hz interference, remove
the shield on one side.
Digital Signals (Enable, Ready, Error, Disable Rev, Disable Fwd)
No shielding required.
To verify a trouble-free operation and the conformity to CE regulation, it makes only sense
to test the system as a whole, with all components installed (motor, amplifier, supply pack,
EMC filters cables etc.).
Note: To improve the noise immunity, always connect unused logical inputs to a fix
potential.