USER MANUAL AIR SOURCE HEAT PUMP MODEL: AWA-SS-6 AWA-SS-8 AWA-SS-8 AWA-SS-10 AWA-SS-12 AWA-SS-16 - ALL IN ONE- (230V/50H Z ) (3x400V/3/50H Z ) -Please read this operating manual before using the Heap Pump- TYDP
List of contents 1 Important Information……………………………………………………..3 1.1 1.1.1 1.1.2 1.1.3 1.2 1.2.1 Safety Instructions………………………………………………………………..3 Installation and Maintenance ……………………………………………………...3 Modification of System Components……………………………………………….3 Safety Valve……………………………………………………………………...3 Protective Measures…………………………………………………………..…..3 Preventing Corrosion ..…………………………………………………………...3 2 Unit Description ……………………………………………………….…….3 2.1 Heat Pump Principle ………………………………………………………..….4 2.
1 Important Information * If the installation will be shut down during the winter months, the heating system should be emptied of water to avoid any damage due to freezing.(Call your Installation Contractor for help, see ”References” on page 30). * The installation is practically maintenance free, but some monitoring will be required (see ”Operating Instructions” on page 7). * Before making any adjustments of system parameters, first find out, what the consequences are in each case.
an immersion heater. The Tap Water Stratification system improves the efficiency of heat transfer by keeping the water in distinct thermal layers in the water tank. The unit is fitted with a regulating computer, which is controlled over a graphic display unit. Heat is distributed throughout the house over a hydronic heating system referred to as low temperature system with a maximal water temperature to radiators ( Feed line temperature) of 65°C.
. The heat pump has two separate liquid circuits circuit – circulating inside the heat pump. Through evaporation, compression and condensation it absorbs energy from the outdoor unit and releases it to the heat carrier. The refrigerant is chlorine-free. Refrigerant Heating circuit – water transporting heat energy to the heating system (radiators/floor coils) and the water heater.
AWA-SS 2.4 Control Panel The control panel of AWA-SS series features a graphic display, five control buttons. Beside the control panel you will find the User’s Manual, a short description of how to increase and reduce room temperature, and a label with name and phone number of dealer. ROOM 20 OPER.
ROOM 20 OPER. WA R M WAT E R 11:30 MONDAY 1 Control Buttons ˄influence key˅ 2.4.1 Functions The control computer is operated with the help of a user friendly menu system that is displayed on the control panel. There is a main menu and several sub-menus accessible from the main menu. The menus are described in detail further down. To be able to select the desired menu and increase or reduce preset values, you will use the five buttons.
Symbols For you to know at a glance the actual operating mode of the heat pump, each of the following symbols will be shown in the lower part of the display depending on which part of the unit is working: 1. The heat pump is running. 2. The auxiliary heater is activated. 3. There is a room heating demand. 4. Warm water is being produced. 5. Indicates the status of warm water production. If the symbol is empty, warm water temperature is under the setting temperature.
3.1.2 Menus 3.1.2.1 Main Menu INFORMATION To open the main menu INFORMATION, press the right- or left-hand button once. Return Open next menu INFORMATION OPERATION HEATCURVE TEMPERATURE INTEGRAL OPER.TIME RESET MAN TEST DEFROST SETTING LANGUAGE Sub menus To select the desired sub-menu, use the up or down button. Open the menu by pressing the right-hand button once. To return to the main menu, press the left-hand button once. OPERATION Running mode: Room heating 1, Room heating 2,Water tank heating.
3.1.2.2 Sub-Menu OPERATION OPERATION ROOMHEAT 1 ROOMHEAT 2 WARMWATER HEATPUMP ADD.HEAT ON ON ROOMHEAT1᧶ After select mode ROOMHEAT 1, the heat curve is that feed water temperature determined by outdoor ambient temperature. At the time, ROOMHEAT2 be of no effect. ROOMHEAT2᧶ After select ROOMHEAT 2, feed water temperature is adjustable from 10 to 65ć, factory setting is 45ć.
3.1.2.3 Sub-Menu HEAT CURVE This menu is used for making adjustments that affect the room temperature.For more information, please refer to ”Adjustments to be made regularly” on page 20. HEATCURVE CURVE MIN MAX CURVE 5 CURVE 0 CURVE -5 HIGH T° STOP LOW T° STOP -50 40 22 70 0 0 0 50 Table 1: Menu– HEAT CURVE Menu Text CURVE MIN Description The value entered shows the temperature of the water to be distributed to the radiators (feed water temperature) when the outside air temperature is 0°C.
3.1.2.4 Sub-Menu TEMPERATURE This menu shows the different temperatures of the heating system. All temperature changes registered over the last 60 minutes are stored in the control system and can be viewed in the shape of graphs. TEMPERATURE OUT ROOM FEED. RETURN WARMWT PIPE 25 28 30(65) 45 30(50) 22 OUT˖Display outdoor ambient temperature. ROOM ˖ Display room air temperature. FEED˖ 1.
Integral (DM) is a program to set the startup time and distance between compressor and electrical heater according to heat demand and heat output, to set stop conditions of compressor and electrical heater. This program is depends on the "feed water temperature degeneratiaon" and Time. To enter this menu operator can change the factory setting: Menu Text OFF CMP.A ADD1 ADD2 ADD3 Description When the value (testing) reaches the value setting by user, the system will be closed.
Before the Degree Minute reach - 60 (adjustable) ,the compressor is off, but when the Degree Minute reach - 60 (adjustable) ,the compressor automatic start, and the flow temperature will begin increase. (Higher than desired temperature) when the actual water supply temperature reach / higher than the desired temperature, the DM will be changed. For example : the DM was cumulated to -160 in this time. 1 minutes later when the Feed water temperature higher than desired temperature for 1ć.
3.1.2.6 Sub-Menu OPERATING TIME OPERATION TIME HEATPUMP ADD 1 ADD 2 ADD 3 Menu Text HEATPUMP ADD1 ADD2 ADD3 3.1.2.7 0 H 0 H 0 H 0 H Description Adjustable by Total operating hours of heat pump since installation. Operating time will not be reset to zero. can not Total operating hours of auxiliary heater (3kW) since installation. Operating time will will not be reset to zero. can not Total operating hours of auxiliary heater (6kW) since installation.
3.1.2.9 Sub-Menu DEFROST How to enter the Sub-Menu DEFROST: You need to choose the "DEFROST"on the main menu ( INFORMATION). Press the right button.Then "DEFROST"menu can be seen. You can choose "Intell Defrost"or "Manual Defrost" DEFROST INTELL. DEF. MANUAL. DEF. DEF. TIME INTERVAL START TEMP EXIT TEMP SINCE TIME 0 M 1 BETW. TIME DEF. ADD 15 M 40 M -4 15 0 M INTELL.
When choose Intelligent defrost mode, the Defrost start temperature will be the same as above form when the ambient temperature is lower than 2 degree, all the value of the form is factory setting and they are adjustable from 0 to -30 degree. Press button Right 5 seconds to enter the form, operator can select any defrost start temperature and revise it.
3.1.2.10 Sub-Menu SETTING How to enter the Sub-Menu SETTING: You need to choose the "SETTING"on the main menu ( INFORMATION). Press the right button.Then "SETTING"menu can be seen. SETTING DATE TIME TIME TIMER 1 ON TIMER 1 OFF TIMER 2 ON TIMER 2 OFF ADD.HEAT TIMER MON 11:30 X X X X DATE TIME To display or adjust day of week. Double timer function: TIMER1 ON ˖¥ 9˖00 TIMER2ON ˖¥ 14˖00 TIME ON (ON)21:00-08:00(OFF) WARMWT TIMER (ON)18:00-22:00(OFF) CMPDIF TEMP EMERGENCY 1 EMERGENCY 2 OUT ADD.
EMERGENCY2(ONorOFF) Emergency mode 2˄ emergency 2˅˄ : ON or OFF˅ˈfactory setting is OFF: (after select emergency mode, the unit will continuously execute the same objective (room heating only, water tank heating only, or auto) When select this mode, compressor will stop determined by outdoor ambient temperature, the temperature setting is from 0 to -50 degree adjustable, factory setting is -25 degree, only electrical heater, water pump or other temperature protection are available.
3.1.2.11 Sub-Menu LANGUAGE Language selection : How to enter the Sub-Menu of LANGUAGE: You need to choose the "LANGUAGE"on the Main menu ( INFORMATION ). Press the right button.Then "LANGUAGE"menu can be seen. LANGUANG ENGLISH DEUTSCH Use Up and Down botton to select the language ,and press Right button to confirm. 3.2 Adjustments to be made rregularly Most settings will be made by the installation contractor in connection with installation.
CURVE is program that adjusts feed water temperature according outdoor ambient temperature, factory setting is ambient temperature 0ć as feed water temperature 40ć, that is CURVE =40; the value of CURVE is adjustable from 22ć to 56ć.
If you wish to change the ROOM value: 1 Press the ”up” or ”down” button once to open the ROOM value for adjustment. 2 Increase or reduce the preset value using the ”up” or ”down” button so that the desired room temperature is reached. Wait for 10 seconds or press the left-hand button once to return to the main menu. When enter ‘Room heat’ mode, user could control compressor and electrical heater through regulate heat curve or DM (degree minute).
3.2.4 Adjustment of Part of the Heat Curve At outdoor temperatures between -5°C and +5°C part of the heat curve may need adjusting if the indoor temperature does not stay at the preset ROOM value. For this reason, the control system includes a function adjusting the curve at three outside temperatures: -5°C, 0°C, +5°C. This function will allow you to increase or reduce the feed line temperature, without affecting the heat curve, at three specific outdoor temperatures.
If you wish to change a specific part of the heat curve: 1. Open the main menu INFORMATION by pressing the right-hand button once. You will find the cursor at the sub- menu OPERATION. 2. Press the ”down” button to move the cursor to the sub-menu HEAT CURVE. 3. Open the selected menu by pressing the right-hand button once. You will find the cursor at the parameter CURVE. 4. Using the ”up” or ”down” button, select either CURVE 5, CURVE 0 or CURVE -5. 5.
3.2.6 Adjustment of the HIGH T STOP and LOW T STOP ‘HIGH T STOP’ and ‘LOW T STOP’ functions are only for room heating, the water tank heating still works normally when the two functions are active. The HIGH T STOP and LOW T STOP function stops water production to room floor when the outside air temperature is equal to higher or lower than the value entered for HIGH T STOP or LOW T STOP. When the function is activated, the circulation pump will be turned off. The factory setting of the HIGH T STOP is 50°C.
3.3 Maximum Return Line Temperature The maximum return line temperature, i.e. temperature of the water returning from the heating system, should be adapted to each individual installation. The correct temperature value for your system will be entered by your installation contractor in connection with installation and can be adjusted later. 3.4 Warm Water Production The temperature of the water distributed to the water heater is controlled by the regulating pressure switch and cannot be adjusted.
Don’t use any water treatment additives for the heating system! 3.5.3 Checking the Safety Valves Both safety valves of the heating system should be checked at least four times a year to prevent lime deposits to clog the mechanism. To find out where the safety valves are located. The safety valve of the water heater protects the closed heater against positive pressure. It is fitted on the cold water inlet line, its outlet opening facing down- wards.
4 Trouble shooting 4.1 Alarm Messages In the event of an alarm message, try to re-start the unit with the safety switch. If this does not work, try to solve the problem with the help of the table below. Call your installation contractor if you need help. See ”References” on page 30.
5 Terminology and Abbreviations Evaporate In the evaporator, energy from the heat source is absorbed by the refrigerant passing through the evaporator. The refrigerant turns into gas. (See ”Heat Pump Principle” on p. 4). INTEGRAL INTEGRAL is the heat balance of the heating system. Production of heat is regulated acc. to a calculated heat demand value. This value is determined by comparing the actual supply line temperature with its calculated (setpoint) value.
6 Default Settings The first column of table 7 shows the parameters that are adjustable by the User. The second column shows settings made at the factory and the third column the settings made by the installation contractor in connection with installation of the heat pump. Make sure that the installation contractor enters any settings made during installation that are particular for your heat pump. This will make it easier for you when you make your own adjustments.