Specifications

32
Natatorium DesigN maNual
Ensure an appropriate maximum ambient air
temperature has been specified.
Ensure the unit has proper airflow.
A perimeter of free area equal to its width
must be provided.
Use line sizes as specified by Seresco.
To avoid potential seasonal system charge
problems with outdoor condensers, ensure
the installed line lengths are never longer than
indicated on the plans and specifications.
If the condenser is installed above the
dehumidifier, ensure the hot gas line has
proper oil traps.
Contact Seresco if the condenser is
installed more than eight (8) feet below the
dehumidifier.
Figure 22 – Typical Outdoor Condenser Installation
Figure 21 – Typical Outdoor Condenser Installation