Specifications
32
Natatorium DesigN maNual
• Ensure an appropriate maximum ambient air
temperature has been specified.
• Ensure the unit has proper airflow.
A perimeter of free area equal to its width
must be provided.
• Use line sizes as specified by Seresco.
• To avoid potential seasonal system charge
problems with outdoor condensers, ensure
the installed line lengths are never longer than
indicated on the plans and specifications.
• If the condenser is installed above the
dehumidifier, ensure the hot gas line has
proper oil traps.
• Contact Seresco if the condenser is
installed more than eight (8) feet below the
dehumidifier.
Figure 22 – Typical Outdoor Condenser Installation
Figure 21 – Typical Outdoor Condenser Installation