Specifications
        25 
6.2. Mechanical System Troubleshooting 
Issue Possible Cause Remedy 
Supply blower will not start 
Firestat contact closure  Check firestat switch 
Loss of main power 
Check for tripped circuit 
breaker or blown fuses 
Manually shut down on 
controller 
Restart 
Faulty control wiring 
Check for loose or incorrect 
wires on system and controller 
Faulty wiring 
Check for loose or faulty wiring 
on system and controller 
Motor windings have shorted  Replace motor 
Blower overload has tripped  reset overload 
Compressor will not start 
Manually shut down on 
controller 
Restart 
Faulty control wiring 
Check for loose or incorrect 
wires on system and controller 
No demands to run 
Adjust setpoints to what is 
indicated on the unit 
Nameplate 
Loss of main power 
Check for tripped circuit 
breaker or blown fuses 
Blower not operating 
Refer to supply blower 
problem section 
Faulty wiring 
Check for loose or faulty wiring 
on system and controller 
Compressor thermal protector 
is open 
Allow one hour for compressor 
to cool off. 
Compressor delay-timer  Wait 3 minutes for timer 
Compressor overload has 
tripped 
Correct cause and reset 
overload 
Compressor draws locked 
rotor amps 
Replace compressor (or check 
fuses on three-phase units) 
Motor windings have shorted  Replace compressor 
Compressor starts but does 
not pump 
Replace compressor 
Low Suction pressure 
Normal: 60 – 75 PSIG 
Excessive bubbles in sight 
glass (more than 10% of 
volume) 
Lack of refrigerant. Check 
receiver sight glasses –level 
indicators. Is the bottom ball 
floating? 
Blocked filter drier. 
Return air is below 70°F 
Is cold outdoor air mixing 
upstream of the coil? 
Too much cold outdoor air 
being introduced to the space. 
Duct heater not able to 
accommodate actual load. 
Review space heating 
requirement. 










