Specifications
        23 
4.3.6 Compressor Start Sequence 
All NE units have a pump down sequence 
and anti-short cycle timer. When a demand 
requires the compressor to operate the 
following sequence occurs: 
  Blower operation confirmed by 
microprocessor and ASCT sequence 
completed. 
  Pump down solenoid opens. 
  50 psig will close the low pressure 
safety switch contact. 
 Compressor starts.  
4.3.7 Space Heat Demand (Unit Mounted 
or remote) 
The Seresco unit’s microprocessor is 
designed to control a space-heating coil 
(unit mounted or remote). When the room 
temperature drops below the set point the 
microprocessor will send a signal to the 
heating coil’s control mechanism. 
5. Service and Maintenance 
The NE unit is a piece of mechanical 
equipment, which requires routine 
maintenance and service. The service 
required is nothing more than a traditional 
commercial air conditioner. If a problem is 
encountered, refer to the T
ROUBLESHOOTING 
GUIDE in Section 6.2. 
If all suggestions in the “Trouble shooting 
guide” have been exhausted, call Seresco’s 
service department. Be sure to have the 
Model and Serial number when you call. 
1-888-SERESCO (737-3726) 
If the unit has been ordered with the internet 
connection capabilities, Seresco or the local 
factory representative can directly access 
the unit and diagnose the problem from their 
facility. 
5.1. Routine Maintenance 
Seresco dehumidifiers are designed for 
years of reliable service. In order to ensure 
this, they require periodic maintenance. 
5.1.1 Monthly Service 
  Check the air filters and replace them if 
necessary. 
  Check all water connections for leaks 
and ensure all hose clamps are tight. 
5.1.2 Annual Service 
  Tighten all field and factory electrical 
connections. 
  Verify that the coils in the dehumidifier 
and the remote outdoor air-cooled. 
condenser or dry cooler are clean. Use 
compressed air or a commercial coil 
cleanser if they are dirty.
 
Verify that the airflow around the remote 
condenser or dry cooler remains 
unobstructed.
  Check drainpan and clean out any 
residue that may have accumulated. 
  Conduct a complete system check up. 
This requires the service technician to 
fill out page #2 of the Warranty 
Registration and Start-up Report. A 
copy of this worksheet is located on 
page 34. This form is a valuable 
maintenance tool, which can help to 
uncover problems before they get 
expensive. 
5.2  Compressor Replacement
Compressor failures can be caused by: 
liquid slugging, air or moisture in the 
refrigerant circuit, solid contaminants, 
excessive heat or electrical service 
malfunctions. To avoid repeated failures, the 
cause of the failure must be determined and 
then corrected. If the compressor has failed 
because its’ motor has burned out, the 
refrigerant, oil, and piping is contaminated. 
The procedure in section 5.2.1 should be 
followed to replace the compressor and 
clean the refrigerant system. 
All acid must be removed from the 
system to avoid future burnouts. 
Use an oil test kit to determine the severity 
of the burnout. Be sure to follow directions 
provided by the test kit manufacturer for 
complete system cleansing and acid 
removal. Make sure you use rubber gloves 
and eye protection, as contaminated 
refrigerant and oil can cause severe burns! 
5.2.1 Compressor Burnouts 
If the compressor has failed due to a 
burnout, the entire refrigerant charge has 
been contaminated. In the service mode, all 
solenoid valves can be opened in order to 
evacuate the circuit completely. On systems 
equipped with an optional pool water 
condenser, take care to avoid freezing the 
condenser during evacuation. 










