Specifications
        14 
Figure 14 – Perimeter Below Grade Duct Layout 
General Recommendations: 
  Galvanized sheet metal ducts are 
acceptable in most installations. A 
below-grade duct system should use 
PVC or plastic-coated galvanized spiral 
pipe to avoid deterioration. 
  Ductwork that passes through an 
unconditioned area should be insulated 
on the exterior. 
  When applicable, locate exhaust fan 
air intakes as close to the whirlpool as 
possible. 
  To prevent excessive vibration noise, 
install neoprene flex connectors when 
attaching ductwork to the 
dehumidifier. 
  Skylights require significant airflow to 
avoid condensation on their surfaces. 
2.6.2 Evaporation and Latent Loads 
Every building’s moisture (latent) load is 
calculated in the same way. There are 
generally three sources of moisture that are 
considered:
  Internal load; evaporation rate 
 Occupants  
  Outdoor air load 
It is important to be aware of the design criteria 
used to calculate the total load and reconcile a 
unit selection. Seresco’s Natatorium Design 
Manual has more information on this subject. 
2.6.3 Required Access Space 
 Access Space 
No Access = no service or maintenance. 
All NE series dehumidifiers have been 
designed to require only two sides access. 
Allow a minimum of 36 inches of clearance 
on the sides indicated in Figure 15 for piping 
and service access. Mirror access units are 
also available. 
Figure 15 – Recommended Access Space 










