User's Manual

SNAP OFF TAB FOR
TAMPER LOCK
TAMPER RELEASE TAB
MOUNTING HOLES
Figure 2: Tamper-Resistant Feature
Installing the Mounting Base
The mounting base can install directly to standard
single-gang electrical boxes, 4-inch square or octagonal
boxes, 3.5-inch octagonal boxes, or directly mounted to
a wall or ceiling using drywall fasteners.
Select a sensor location using applicable
requirements and the guidelines presented in the
Installation section of this manual.
Separate the mounting base from the unit by turning
the smoke detector counterclockwise.
Secure the mounting base to the desired surface. If
mounting onto plaster or dry wall, use appropriate
anchors.
Align the molded line on the base with the raised
marks on the smoke detector and turn clockwise to
lock in place.
To remove the smoke detector from the base, simply
twist counter-clockwise to unsnap.
Programming
The following instructions provide a guideline for pro-
gramming the SMK into system memory.
To enroll a SMK into system memory:
Enter program mode (NEXT + NEXT + NEXT +
<Prog> + Installer PIN)
The keypad will display “Devices Available.” Select
<Learn>. The display shows “Auto Enroll On.
To enroll the SMK, insert a small screwdriver
or allen wrench (0.18˝ max.) into the test switch
opening; push and hold. Alternatively, activate
the alarm by using Smoke! in a Can®” or direct
actual smoke into the smoke chamber until an alarm
occurs.
Upon enrollment, the keypad emits one beep and the
display shows the zone number and sensor ID.
Continue enrolling additional sensors if desired.
When finished, press <Done> to exit.
1.
2.
3.
4.
5.
1.
2.
3.
4.
5.
Testing
The following steps provide a general procedure for
testing the smoke detector.
Smoke Entry
Test the detector for smoke entry using one of the fol-
lowing methods:
Use “Smoke! in a Can®” and follow the directions
on the can.
Hold a smoldering punk or cotton wick close to
the unit and gently direct the smoke into the smoke
chamber for 20 seconds or until an alarm occurs.
Test Switch
An opening for the recessed test switch is located on
the detector housing (See Figure 4).
Insert a small screwdriver or allen wrench (0.18˝
max.) into the test switch opening; push and hold.
If the detector is within the listed sensitivity limits, the
detector’s red LED should light within one second.
LEDS
RECESSED TEST SWITCH
Figure 3 Recessed Test Switch
Walk Test
Press NEXT + NEXT and the keypad will display
LOG TEST RESET.
Select <Test> and enter the installer or user PIN.
The display will show WALK COMM.
Select <Walk> and the keypad will display “Walk
Test Active.”
Trip each zone/sensor one at a time and the system
responds with a tone from the keypad.
As each tested sensor is added to a scrolling list of
tested sensors, the signal strength will be shown on
the LCD display as 1-10. A higher value indicates
a stronger signal level. A minimum level of five is
recommended.
Exit walk test mode by pressing <Done>.
1.
2.
3.
1.
2.
3.
4.
5.
6.
2