Instruction Manual
INSTALLATION INSTRUCTIONS
senvainc.com 1-866-660-8864 (F)1-503-296-2529 9290 SW Nimbus Ave. Beaverton Oregon 97008
EMX True RMS Energy Meter
With Traditional Metering CTs
BACnet/Modbus/Pulse
LIMITATION OF LIABILITY
Senva’s liability, whether in contract, in tort, under any
warranty, in negligence or otherwise shall not exceed the
amount of the purchase price paid by the purchaser for the
product. Under no circumstances shall Senva be liable for
special or consequential damages.
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Failure to follow these instructions may cause serious injury or death
Failure to follow these instructions may cause injury, death or
equipment damage.
• If product is used in a manner not specied by the manufacturer,
the protection provided by the product may be impaired.
No responsibility is assumed by the manufacturer for any
consequences arising out of the use of this material.
DANGER
• Do not use this product for life safety applications.
• Do not install this product in hazardous or classied locations.
• Only qualied trade installers should install, program, maintain
and test system incorporated therein. Installer is responsible for
compliance of all applicable codes.
• Read, understand, and follow instructions thoroughly.
• The Standard CTs associated with this product must be mounted
inside a suitable re and electrical enclosure. For safe electrical work
practices, see NFPA 70E in the USA or applicable local standards and
codes.
• Replace all doors, covers, and protective devices before powering
the equipment.
• Product may use multiple voltage/power sources. Disconnect ALL
sources before servicing.
• Use a properly rated voltage sensing device to conrm that power
is o. DO NOT depend on this product for voltage indication.
• The installer is responsible for conformance to all applicable codes.
• For use with Listed Energy Monitoring Current Transformers.
• Use Copper Conductors Only
• Per IEC 61010-1 section 8.2.2 “impact test”, this product tested with
energy of 2J (reduced from 5J) code: IK07
WARNING
!
FEATURES
The Senva EMX Advanced Energy Meter is a 3 channel True
RMS energy meter featuring a color OLED display for simple
commissioning and monitoring. The EMX meets ANSI C12.20
Class 0.2 Standards. The EMX supports both BACnet MS/TP and
Modbus RTU protocols and also includes 2 pulse inputs and 2
pulse outputs.
The EMX supports metering CTs with either a 0.333V voltage
output or di/dt signal. The EMX is a class 2 low voltage device
for mounting exibility. See Specications section for
recommended conductor gauge and terminal tightening
torque.
MOUNTING
The Senva EMX Advanced Energy Meter is suitable for
installation on T35 DIN rail. Simply place unit approximately
centered over the mounted DIN rail and press upward until the
bottom clicks into place. Using a at-nose screwdriver, pull top
tab and apply pressure downward until unit is ush and release
the tab. See Dimensions section for details.
DIMENSIONS
4.183in
106.25mm
3.551in
90.20mm
2.990in
75.93mm
Data
Pulse
Status
Alarm
Press any key to wake
ESC
Press any
key to wake
EMX Advanced
Energy Meter
ESC
1.390in
35.30mm
2.055in
52.20mm
2.323in
59.00mm
.280in
7.10mm
.197in
5.00mm
1.134in
28.80mm
.098in
2.50mm
WIRING
EMX Wiring
Using Traditional metering CTs please wire according to the following
diagram.
Wiring for connections labeled “Class 2” shall be permanently
separated from those labeled “Class 1” by a minimum of 6
mm by means of clamping, routing, or equivalent means.
Press any key to wake
ESC
RS485 Ground/Shield
Pulse Input 1
Pulse Input Common
RS485 (+)
RS485 ( - )
COM
IN1
IN2
O1+
O1-
O2+
O2-
+
-
Pulse Input 2
Pulse Output 1+
Pulse Output 1 -
Pulse Output 2 +
Pulse Output 2 -
Phase R/L1/A Line
Phase S/L2/B Line
Phase T/L3/C Line
Neutral
A/L1
B/L2
C/L3
N
-
Phase R +
Phase R -
Shield
Phase S +
Phase S -
Shield
Phase T +
Phase T -
Shield
+
S
Press any
key to wake
EMX Advanced
Energy Meter
ESC
-
+
S
-
+
S
S
Class 1Class 2