Installation guide
 PAGE 24 
cables.  Place the selected fully charged battery with 
full electrolyte in battery tray and secure with battery 
hold down strap. 
Before  connecting  battery  cables  to  battery, 
complete the following steps: 
Battery cables are factory connected at the generator 
points (red engine starter motor (positive) cable and 
black  ground  (negative)  cable).    Electrician  should 
connect the  red battery cable  (from  engine starter 
solenoid point) to battery post shown with “positive”, 
POS,  or  (+)  indicator.    Connect  the  black  battery 
cables  (from  frame  ground)  to  the  battery  negative 
post.    NOTE:  Both  positive  and  negative  battery 
cables have protective “boots” that enclose the cable 
connections  to  battery  posts.    Also,  positive  battery 
cable is secured, so that, if cut or disconnected in any 
way, positive cable won’t touch metal door. 
Dielectric  grease  should  be  used  on  battery  lugs  or 
posts to help in the prevention of normal corrosion. 
Damage  will  result  to  generator  controls,  if  battery 
cables are made in reverse connections. 
Inspect, clean, or re-grease battery connections ever 
60-90 days. 
In  cold  climate  areas,  where  temperatures  normally 
reach 10º  F (-12º  C)  or colder, an  optional battery 
wrap-around  heater,  controlled  by  thermostat, 
should be used, for increased battery power. 
This  generator  is  equipped  with  an  automatic  “float 
type”  3-stage  (bulk,  absorption,  and  float)  battery 
charger,  energized  by  utility  power,  to  maintain  full 
battery  power  while  on  standby  (non-running) 
condition.  CAUTION: This charger can not recharge 
a fully discharged or defective battery. 
● Do  not  dispose  of  battery  in  a  fire.    The 
battery  is  capable  of  exploding  and 
spewing electrolyte in several directions. 
● Do  not  open  up  a  battery.    It  has 
electrolyte  and  is  harmful  to  the  skin  and 
eyes, and is toxic. 
● Battery  electrolyte  is  electrically 
conductive and corrosive. 
The high voltage access panels should only 
be  removed  by  experienced  licensed 
electricians,  repair  and  service  personnel, 
and installers. 
Electrical  shock  from  mishandled 
battery. 
Toxic  fumes  from  battery  or  engine 
exhaust may be inhaled. 
Hot surfaces may cause severe burns. 
Explosions  from  battery  or  dry  fuel 
fumes being  ignited by careless  smoking 
or sparks from mishandled tools. 
All hinged  or bolted  panel contains  access 
to  A-C  and  D-C  dangerous  high  voltage 
electricity.    These  voltages  can  cause  a 
fatal  electric  shock  and  will  cause  sudden  illness, 
dizziness,  and  incoherent  actions.    Only 
experienced licensed  electricians and authorized 
service  technicians  should  have  access  behind 
closed and locked housing doors. 
BATTERY SELECTION & INSTALLATION 
The 12 VDC battery is not furnished with the standby 
generator  set.    The  generator  can  be  installed  in  a 
wide  range  of  temperatures  and  climate  conditions. 
As climates get colder, batteries loose their ability to 
produce  required  power.    Therefore,  battery  size 
must be increased. Installer must provide proper 
battery size, depending on environment. 
Climates that  reach  to a  low of  20º F  (-6.7º  C) can 
achieve good generator  operation with a  12 VDC, 
heavy  duty  battery.    Climates  that  reach  below  this 
temperature  line  should  have  a  10-20%  increase  in 
CCA rating for  a 12 VDC  battery.  See  Battery Chart 
on page 17. (See Figure 8) 
CAUTION:  All  12  VDC  batteries  will loose a  certain 
percent  of  their  charge  while  in  storage.    It  is  very 
important  to  test  the  battery  voltage  before  it  is 
installed  in  generator  and  taken  to  jobsite.    A  fully 
charged  battery must test at  12.5 – 13.0  volts DC. 
Also,  the  correct  battery  must  have  lug  terminals  to 
match  lug  battery  cables,  for  a  bolt-together 
connection.  When  replacing  batteries,  use  the 
same number and the following type batteries: 
    Sealed type:lead-acid 
 (1) 20-60 KW 1800 RPM sets 650 C.C.A. or 55 amp/hour 
 (1) 80-140 KW 1800 RPM sets 710 C.C.A. or 65 amp/hour 
This generator is equipped with a corrosion resistant 
battery tray, a battery hold down strap and battery 
WARNING
DANGER
NOTICE 
DANGER