Programming instructions

11
Controller Power Input Test Result: less than 20 volts
Did you recently replace the transformer? It may be the
wrong voltage. The voltage is below 20, which is not enough
power for the controller. To find out the cause of low volt
-
age, continue below:
Controller Input Test #2
The back of the board is
still facing you and the kiln
is plugged in. Remove the
INPUT plug, which is the
white, orange, and blue
wires, from the back of the
controller. Touch a volt
-
meter probe to the white
wire and the other probe to the orange wire.
Input Test #2 Result: Less than 20 Volts AC
There are two possible reasons: 1) Low voltage at the
wall receptacle; 2) defective transformer. If wall receptacle
voltage is correct, replace the transformer.
Input Test #2 Result: 20 - 24 Volts AC
The transformer is sending correct voltage to the con
-
troller. Yet when the INPUT plug was connected to the
controller, voltage was less than 20. This means the control
-
ler is draining the voltage and is defective. Return the con-
troller for repair or replacement.
Problem: Controller display
turns on. No heat in kiln.
I
Is the relay making its normal clicking sound?
Yes, the relay is clicking.
Test the elements with an ohmmeter:
Element Resistance Test
UNPLUG kiln/disconnect the power. Open the
kiln’s switch box. Make sure the wires connecting
the relay to the elements are secure. If connections
are okay, continue to step 2:
Touch the ohmmeter leads to the two element con
-
nectors of each element. A no-needle-movement
reading on an analog meter, or OPEN on a digital
meter, indicates a broken element.
If the elements check out okay, replace the relay.
Note: To replace relay, see your kiln’s instruction and
service manual.
No, the relay is not clicking.
We know the controller is receiving voltage, because the
display is lit. But the voltage from the transformer may be
too low to power the relays. Perform the “Controller Power
Input Test,” page 10. If your controller passes the input test,
perform the “Controller Power Output Test”:
Controller Power Output Test
Is the controller sending voltage to the relay? Test OUT
-
PUT with a voltmeter:
UNPLUG the kiln/disconnect the power. Remove
the 4 screws holding the controller faceplate to the
switch box. Lift faceplate out of box and let the con
-
troller hang on the outside of the box with the back
of the board facing you. Then plug the kiln back in.
Program the controller to fire to 1000°F at FULL
rate in Ramp-Hold mode. Press .
Put the voltmeter in DC mode. (It must be in DC
mode when testing OUTPUT voltage.) Touch
probes to the red wire and black wire connections.
Measure voltage when the relay clicks on.
Output Test Result: No voltage at red and black wires
The controller is not sending power to the relay. Return
the controller for repair or replacement.
Output Test Result: 10 - 14 v. at red and black wires
The controller is sending correct power to the relay. Un
-
plug kiln/disconnect power. Remove the kiln switch box.
Look for disconnected wires between the controller, relay
and elements. Check the wiring diagram to be sure wires
are connected to the correct terminals. Be sure connections
are tight. If the wiring is okay, replace the relay.
Note: To replace relay, see your kiln’s instruction and
service manual.
Problem: Kiln switch box ½
amp fuses keep blowing.
I
What size fuse are you using? Correct fuse:
AGC ½ A 250V AC.
If the fuse is thecorrectsize, performthe following test:
Kiln Switch Box ½ Amp Fuse Power Test
UNPLUG the kiln/disconnect the power. Remove
the 4 screws holding the controller board faceplate
tothe switch box. Lift faceplateoutof box and letthe
board hang on the
outside of the box
with the back of the
board facing you.
Disconnect both wire
plugs from the back
of the controller.
Then plug the kiln
back in. Apply power to kiln. If the ½ amp fuse
blows, replace the transformer. (If the fuse does not
blow, the problem is a boardor relay. Goto step 2.)
Connect the INPUT plug (orange, blue, and white
wires) to the board again. Leave off the OUTPUT
wire plug (the one with the red, green and black
wires). Program the controller to fire to 1000°F at
FULL rate in Ramp-Hold mode. Press .If
the fuse blows, replace or service the board. (If the
fuse does not blow, the problem is caused by a short
in the coil of a relay. Go to step 3.)
UNPLUG kiln/disconnect power. Reconnect the
OUTPUT wire plug. Reinstall the board in the
switch box. Replace the relay.