Tool Storage - Tool Cabinet User Manual
Displaying system configuration information 
The Show System command displays all system configuration information. 
•  Firmware version 
•  NIC module serial number and MAC address 
•  Hardware revision code and Flash size 
•  Uptime since last system restart 
•  System location description 
See Chapter 4: Advanced Operations on page 41 for more information on SNMP. 
To display system configuration information: 
At the Sentry: prompt, type show system and press Enter. 
Example 
 System Information 
 F/W Version: Sentry Version 5.2b 
 NIC S/N: 1600001 
 MAC Address: 00-0a-9c-10-00-01 
 H/W Rev Code: 0 
 Flash Size: 1 MB 
 Uptime: 0 days 6 hours 14 minutes 1 second 
 Location: Florida HQ 
Creating a descriptive tower name 
The Set Tower Name command assigns a descriptive name to a tower. This descriptive name is 
displayed when the Show Traps command is issued. See Displaying trap configuration information on 
page 34 for more information on the Show Traps command. 
To create a tower name: 
At the Sentry: prompt, type set tower name, followed by the absolute tower name, then the descriptive 
name of up to 24 alphanumeric and other typeable characters (ASCII 33 to 126 decimal - spaces are not 
allowed). Press Enter. 
Examples 
The following command adds the descriptive name Florida_HQ_1 to tower .a: 
Sentry: set tower name .a Florida_HQ_1<Enter> 
Displaying tower information 
The Show Towers command displays information about the Sentry. This information includes the 
absolute and descriptive Sentry names. 
To display tower information: 
At the Sentry: prompt, type show towers and press Enter. 
Example 
Sentry: show towers<Enter> 
 Tower Tower 
 ID Name 
 .A Florida_HQ_1 
Creating a descriptive infeed name 
The Set Infeed Name command assigns a descriptive name to an infeed. This descriptive name is 
displayed when the Show Traps command is issued. See Displaying trap configuration information on 
page 34 for more information on the Show Traps command. 
To create a infeed name: 
At the Sentry: prompt, type set infeed name, followed by the absolute infeed name, then the descriptive 
name of up to 24 alphanumeric and other typeable characters (ASCII 33 to 126 decimal - spaces are not 
allowed). Press Enter. 
Example 
The following command adds the descriptive name HQ_1_Infeed_A to the infeed on the Sentry: 
Sentry: set infeed name .aa HQ_1_Infeed_A<Enter> 
34 • Operations  Sentry Commander - PT40 
    Installation and Operations Manual 