Tool Storage - Tool Cabinet User Manual
Outlet Control 
The Outlet Control section offers access to the Individual and Group outlet control pages. From the 
Individual and Group pages, the user can review and manipulate power control functions for all outlets 
and groups assigned to the current user. Both pages include the outlets absolute and descriptive names, 
the Outlet Status reported to the Sentry by the outlet, the current Control State being applied by the 
Sentry and the outlet load in amperes. 
Available outlet and group power states may be set to on, off or reboot; the reboot operation turns the 
outlet(s) off, delays for a period of 15 seconds and then turns the outlet(s) on. 
Individual 
The Individual outlet control page displays all outlets assigned to the current user. The user may apply 
on, off or reboot actions to individual, multiple or all accessible outlets. 
To apply actions to individual or multiple outlets: 
In the Individual Outlet Control section, select the desired action from the Control Action drop-down 
menu for each individual outlet to be changed and press Apply. 
To apply an action to all outlets: 
In the Global Control section, select the desired action from the Control Action drop-down menu and 
press Apply. 
Group 
The Group outlet control page displays all groups assigned to the current user as well as the outlets for 
each group. 
To select a group: 
Select the group name from the drop-down menu and press Select. The page will refresh to display all 
outlets associated to the selected group name. 
To apply an action to a group: 
Select the desired action from the drop-down menu and press Apply. 
Outlet State/Control State Field Values 
Outlet State  Control State  Description   
On  On  Outlet is on 
Off  Off  Outlet is off 
Off  Pend On  Outlet is off and about to turn on in response to a sequence timer 
Off  Reboot  Outlet is off and a Reboot action has been initiated 
On  Idle On  A restart has occurred – Last Control State has been maintained 
Off  Idle Off  A restart has occurred – Last Control State has been maintained 
On  Wake On  A power-loss has occurred – Wakeup State has been applied 
Off  Wake Off  A power-loss has occurred – Wakeup State has been applied 
On/Wait  Off  Outlet state in transition – Requery of outlet status required 
Off/Wait  On  Outlet state in transition – Requery of outlet status required 
On/Error  varies  Error State – Outlet should be off but current is sensed at the outlet 
Off/Error  varies  Error State – Outlet should be on but no current is sensed at the outlet 
No Comm  varies  Communication to the outlet has been lost* 
* Control State will be applied when communication is re-established 
Environmental Monitoring 
The Environmental Monitoring section offers access to the Input Load page. This section is available 
to administrative level users and users with Environmental Monitoring view rights. 
Input Load 
The Input Load page displays the tower(s) absolute and descriptive name and the cumulative input load 
in amperes of all devices attached to the Sentry at the time the page was loaded. This page will refresh 
automatically every 10 seconds. 
12 • Operations  Sentry Commander - PT40 