Product Overview

Application
1. If Sentinel X100 has just been added to the system, allow it to circulate for at least one hour before carrying out
the test so that the product is distributed evenly throughout the entire circuit.
2. Add system water to the tube, lling to a level just above the 5ml mark.
3. Place a No 1 tablet and a No 2 tablet into the test tube.
4. Cap the tube and shake vigorously to dissolve.
5. Wait 10 minutes.
6. Hold the tube horizontally over the ‘White Band’ and compare to the ‘Standard’ yellow band.
7. If the colour is deeper or same depth of colour than the ‘Standard’ yellow band, the system treatment is
satisfactory.
8. If the colour is lighter add more Sentinel X100 to the system, allow to circulate and repeat the test
Test Kit Contents
1 Test Tube
2 Sentinel No 1 Tablets
2 Sentinel No 2 Tablets
1 Colour Comparison Chart