User's Manual

13
To be used only for the purpose for which it is submitted. All rights reserved to AMDS LLC. Reproduction without written
consent is prohibited.
AMDS CONFIDENTIAL
3.3. Indicators
Indicator Location Description
INPUT OK Power Supply GRN – Input voltage within normal
operating limits
FAULT Power Supply RED – Output Voltage Fault
GRN – Fusion Processor Power OKPOWER Fusion Processor
OFF – Fusion Processor Power Fail
RED – Alarm Input Active IN1 thru IN7 Fusion Processor
OFF – Alarm Input not Active
TRIP CPC Flash RED – Trip Detected
MSG CPC Flash AMBER – Valid Message
Received
GRN – CPC Power OK OK CPC
OFF – CPC Power Fail
RED – System RESET Asserted RESET A/D
OFF – System OK
GRN – A/D Power OK POWER A/D
OFF – A/D Power Fail
OTR A/D Flash AMBER – Input Over-range
GRN – Receiver Power OK POWER Receiver
OFF – Receiver Power Fail
AMBER – Synthesizer Locked LOCK Receiver
RED – Synthesizer Unlocked
GRN – AC Power OK AC POWER
OK
Rectifier
OFF – AC Power Fail
RED – DC Output Voltage Out of
Range
RECTIFIER
FAILURE
Rectifier
OFF – Normal Operation
RED – Load Fuse Failed LOAD FUSE
FAILURE
Rectifier
OFF – Normal Operation
RED – Output Voltage Low, or
Low Voltage Disconnect
Activated, or
Switch in BYPASS
BATTERY
FAILURE
Rectifier
OFF – Normal Operation
Shaded areas indicate Normal Operation.
3.4. Low Voltage Alarm and Disconnect
Upon Commercial AC Power Failure, the TGB will immediately notify the
network via the AC POWER Alarm; at which time the system will begin
operating on battery backup. After duration determined by capacity of
batteries, charge state, temperature, and current draw, the output voltage of
the batteries will decrease.