User's Manual
The following document and its attachments are considered proprietary and confidential and the Property
of Sensus Metering Systems Inc. To be used only for the purpose for which it is submitted. All rights are
reserved to Sensus Metering Systems Inc. Reproduction without prior written consent is prohibited.
SENSUS CONFIDENTIAL
FlexNet Activation Instructions:
Power up the FlexNet 900 Tool unit by pressing the power button.
The GPS LINK OK led will begin flashing RED at a 1Hz rate.
Carry the unit outside in an area free from overhead obstructions so that the unit can
acquire a GPS position fix. (This takes approximately 1~2 minutes)
Once the unit has acquired a current GPS fix, the GPS LINK OK led will light solid
green. (The light may blink green if the tool temporarily loses a GPS position fix if the
tool is brought indoors or there is significant overhead obstructions)
Once a GPS fix has been acquired, place the tool against the side of the GCVTF unit as
shown in the picture above. The CT should be facing down, and the tool should be
placed on the right side of the unit with the “COMMAND METER” text pointing toward
the center of the Visual Line Status Indicator (VLI).
Press the INSTALL METER button to begin the activation sequence.
The sequence is complete when the METER INSTALL OK light illuminates GREEN
indicating a successful install. (This process should take approximately 30 seconds)