User manual

Sensorsoft Alert User Manual
ssCommandOnBooleanCriticalEnable
DESCRIPTION
: A zero value disables this command line alert. A value of one enables this
command line alert. When enabled, this command line is executed when the currently indexed
variable on the currently indexed device enters Breach of Boolean Critical Limit status. It will be
sent periodically using the time interval in minutes specified by
ssCommandOnBooleanCriticalInterval.
TYPE
: Integer
ACCESS
: Read/Write
OID
.1.3.6.1.4.1.15848.1.71.0
Non-volatile
ssCommandOnBooleanCriticalInterval
DESCRIPTION
: The time interval in minutes between command line execution when the
currently indexed variable enters Breach of Boolean Critical Limit status. A zero value disables
this command.
TYPE
: Integer
ACCESS
: Read/Write
OID
.1.3.6.1.4.1.15848.1.72.0
Non-volatile
ssCommandOnReturnToNormal
DESCRIPTION
: This is the command-line string that will be executed by the shell when the
currently indexed variable on the currently indexed device enters Returned To Normal status.
TYPE
: String
ACCESS
: Read/Write
OID
.1.3.6.1.4.1.15848.1.73.0
Non-volatile
ssCommandOnReturnToNormalEnable
DESCRIPTION
: A zero value disables this command alert. Any other value enables this
command alert. When enabled, this alert is sent only once."
TYPE
: Integer
ACCESS
: Read/Write
OID
.1.3.6.1.4.1.15848.1.74.0
Non-volatile
72