ssCommandOnScalarCriticalLow
DESCRIPTION
: This is the command-line string that will be executed by the shell when the
currently indexed variable on the currently indexed device enters Breach of Critical Low Limit
status.
TYPE
: String
ACCESS
: Read/Write
OID
.1.3.6.1.4.1.15848.1.67.0
Non-volatile
ssCommandOnScalarCriticalLowEnable
DESCRIPTION
: A zero value disables this command line alert. A value of one enables this
command line alert. When enabled, this command line is executed when the currently indexed
variable on the currently indexed device enters Breach of Critical Low Limit status. It will be sent
periodically using the time interval in minutes specified by
ssCommandOnScalarCriticalLowInterval.
TYPE
: Integer
ACCESS
: Read/Write
OID
.1.3.6.1.4.1.15848.1.68.0
Non-volatile
ssCommandOnScalarCriticalLowInterval
DESCRIPTION
: The time interval in minutes between command line execution when the
currently indexed variable enters Breach of Critical Low Limit status.
TYPE
: Integer
ACCESS
: Read/Write
OID
.1.3.6.1.4.1.15848.1.69.0
Non-volatile
ssCommandOnBooleanCritical
DESCRIPTION
: This is the command-line string that will be executed by the shell when the
currently indexed variable on the currently index device enters Breach of Boolean Critical Limit
status.
TYPE
: String
ACCESS
: Read/Write
OID
.1.3.6.1.4.1.15848.1.70.0
Non-volatile
71