User manual

Sensorsoft Alert User Manual
currently indexed device’s location. The dollar variable $U, will be expanded to the location of
the Alert appliance. The dollar variable $R, will be expanded into the currently indexed variable
on the currently indexed device's current reading. The dollar variable $T, will be expanded into the
current date and time.
TYPE
: String
ACCESS
: Read/Write
OID
.1.3.6.1.4.1.15848.1.54.0
Non-volatile
ssEmailOnReturnToNormalMessage
DESCRIPTION
: This is the message of the email that will be sent when the currently indexed
variable on the currently indexed device enters Returned To Normal status. The message line can
also contain the dollar variables: $L, $U, $R, $T and $N. The dollar variable $L, will be expanded
to the currently indexed device’s location. The dollar variable $U, will be expanded to the
location of the Alert appliance. The dollar variable $R, will be expanded into the currently
indexed variable on the currently indexed device's current reading. The dollar variable $T, will be
expanded into the current date and time. Finally, the dollar variable $N, will be expanded into a
newline character so that the message is easier to read
TYPE
: String
ACCESS
: Read/Write
OID
.1.3.6.1.4.1.15848.1.55.0
Non-volatile
ssEmailOnReturnToNormalAddresses
DESCRIPTION
: This is a comma separated list of email recipients that will be sent an email when
the currently indexed variable on the currently indexed device enters Returned To Normal status.
TYPE
: String
ACCESS
: Read/Write
OID
.1.3.6.1.4.1.15848.1.56.0
Non-volatile
ssEmailOnReturnToNormalEnable
DESCRIPTION
: A zero value disables this email alert. Any other value enables this email alert.
When enabled, this alert is sent only once.
TYPE
: Integer
ACCESS
: Read/Write
OID
.1.3.6.1.4.1.15848.1.57.0
Non-volatile
68