User manual
Sensorsoft Alert User Manual
TYPE: String
ACCESS
: Read/Write
OID
.1.3.6.1.4.1.15848.1.46.0
Non-volatile
ssEmailOnScalarWarningEnable
DESCRIPTION
: A zero value disables this email alert. A value of one enables this email alert.
When enabled, this email is sent when the currently indexed variable on the currently indexed
device enters Breach of Warning High Limit status or Breach of Warning Low Limit status. It
will be sent periodically using the time interval in minutes specified by
ssEmailOnScalarWarningInterval.
TYPE
: Integer
ACCESS
: Read/Write
OID
.1.3.6.1.4.1.15848.1.47.0
Non-volatile
ssEmailOnScalarWarningInterval
DESCRIPTION
: The time interval in minutes between emails when the currently indexed variable
on the currently indexed device enters Breach of Warning High Limit status or Breach of Warning
Low Limit status.
TYPE
: Integer
ACCESS
: Read/Write
OID
.1.3.6.1.4.1.15848.1.48.0
Non-volatile
ssEmailOnBooleanCriticalSubject
DESCRIPTION
: This is the subject line of the email that will be sent when the currently indexed
variable on the currently indexed device enters Breach of Boolean Critical Limit status. The
subject can also contain the dollar variables: $L, $U, $R, and $T. The dollar variable $L, will be
expanded to the currently indexed device’s location. The dollar variable $U, will be expanded to
the location of the Alert appliance. The dollar variable $R, will be expanded into the currently
indexed variable on the currently indexed device's current reading. The dollar variable $T, will be
expanded into the current date and time.
TYPE
: String
ACCESS
: Read/Write
OID
.1.3.6.1.4.1.15848.1.49.0
Non-volatile
ssEmailOnBooleanCriticalMessage
DESCRIPTION
: This is the message of the email that will be sent when the currently indexed
variable on the currently indexed device enters Breach of Boolean Critical Limit status. The
message line can also contain the dollar variables: $L, $U, $R, $T and $N. The dollar variable $L,
66